background image

Status Indicators 

Status 

Visual Indication 

Alarm 

AC Mode 

Green Power On LED - On 

Not applicable 

On Battery 

Yellow Batt. Mode LED – Flash  Sounding every 10 seconds 

Low Battery 

Yellow Batt. Mode LED - Flash  Sounding every second 

Battery Replacement  Red Fault LED - On 

Sounding every 2 seconds 

Overload 

Green Power On LED on 

Sounding every 0.5 seconds 

UPS Fault 

Red Fault LED - On 

Continuously sounding 

 

 

 

1. Package Contents 

You should have received the following items inside of package:   

UPS Unit 

User Manual 

USB communication cable 

-    Software CD   

 

 

2. Product Overview 

This compact UPS is to protect your PC data loss from power interruption. This UPS features 

three LED indicators to display the situation of UPS unit.   

 
Top View: 

 

 

Side View: 

 

 

3. Installation & Initial Startup 

NOTE: Before installation, please inspect the unit. Be sure that nothing inside the 
package is damaged.   

 

 
Connect to Utility and Charging 
Plug in the AC input cord to the wall outlet. For the best results, 
suggest to charge the battery at least 4 hours before initial use. 
Please turn on the unit and the unit will charge its battery while 
connecting to the utility. 

 

 
Connect the Loads 
Plug in the loads to output receptacles on the rear panel of the UPS. 
Simply turn on the power switch of UPS unit, then devices connected to 
the UPS will be protected by UPS unit.   

 

CAUTION: NEVER connect a laser printer or scanner to the UPS 
unit. This may cause the damage of the unit. 

 

Connect Modem/Phone/Network to Surge Protection   

Connect a single modem/phone/network line into surge-protected “IN” outlet on the back 

panel of the UPS unit. Connect from “OUT” outlet to the computer with phone line cable.   

 

Connect Communication Cable 

 

To allow for unattended UPS shutdown/start-up and status monitoring, connect the 

communication cable one end to the USB port and the other to the communication 

port of your PC. With the monitoring software installed, you can schedule UPS 

shutdown/start-up and monitor UPS status through PC. 

 

Turn On/Off the Unit 

Turn on the UPS unit by pressing the power switch.    Turn off the UPS unit by pressing again 

the power switch. You may check the Status Indicators Section for the details.     

 

Cold Start Function 

When the UPS is off and there is no power utility, it's still possible to cold start the UPS unit to 

power the loads

 

4. Software Installation & Status Indicators 

Software Installation 

Please follow steps below to download and install monitoring software: 

1. Go to the website http://www.power-software-download.com 

2. Click ViewPower software icon and then choose your required OS to download the 

software.   

3. Follow the on-screen instructions to install the software. 

4. When your computer restarts, the monitoring software will appear as an orange plug icon 

located in the system tray, near the clock. 

5. Important Safety Warning 

 

(SAVE THESE INSTRUCTIONS) 

This manual contains important instructions that should be followed during installation and 

maintenance of the UPS and batteries. 

CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity 

controlled indoor area free of conductive contaminants. (See the specifications for the 

acceptable temperature and humidity range.) 

CAUTION! If the UPS is with metal chassis, for safety purpose, grounding is a must during 

UPS installation in order to reduce leakage current below 3.5A. 

Attention! Hazardous through electric shock.    Also with disconnection of this unit from the 

mains, hazardous voltage still may be accessible through supply from battery. The battery 

supply should be therefore disconnected in the plus and minus pole at the quick connectors 

of the battery when maintenance or service work inside the UPS is necessary. 

 

6. Battery Replacement 

CAUTION! Servicing of batteries should be performed or supervised by personnel 

knowledgeable of batteries and the required precautions.    Keep unauthorized personnel 

away from batteries.   

CAUTION! When replacing the batteries, use the same number and type of batteries. 

CAUTION! Internal battery voltage is 12Vdc. Sealed, lead-acid,6 cells battery. 

CAUTION! Do not dispose of batteries in a fire. The battery may explode. Do not open or 

mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. 

CAUTION! A battery can present a risk of electric shock and high short circuit current. The 

following precaution should be observed before replacing batteries: 

1) 

  Remove watches, rings, or other metal objects. 

2) 

  Use tools with insulated handles. 

3) 

  Wear rubber gloves and boots. 

4) 

  Do not lay tools or metal parts on top of batteries. 

5) 

  Disconnect charging source prior to connecting or   

 

  disconnecting batteries terminal. 

 
Simple steps to replace the battery: 

 

TURN the unit over and Remove the screws located on the 
bottom of the UPS to open the battery cover. 

 

 

LIFT the battery out of the compartment and disconnect the two 
wires connecting it to the UPS. Replace the same type of 
batteries. 

 

 

Slide the battery compartment cover back to the battery 
housing. 

 

 

7. Specification 

 

INPUT 
Model Name 

QUATTRO 600 

QUATTRO 700 

QUATTRO 800 

Capacity 

330W 

375W 

450W 

Voltage 

220/230/240VAC 

Voltage Range 

  170-285VAC   

OUTPUT 
Voltage Regulation (Batt. 

Mode)

 

±10% 

Transfer Time 

Typical 2-6ms, 10ms max. 

Waveform (Batt. Mode) 

Simulated Sine Wave 

BATTERY 
Type & Number 

12V/7A

H x 1  12V/7AH x 1 

12V/9AH x 1 

Recharge Time 

4 hours recover to 90% capacity 

PHYSICAL 
Dimension, DXWXH (mm) 

292 x 199 x 91 (Foot included) 

Net Weight (kgs) 

5.08 

5.3 

5.88 

ENVIRONMENT 
Humidity 

0-90% RH @ 0- 40°C (non-condensing) 

Noise Level 

Less than 40dB 

INTERFACE 
USB Port 

Supports Windows 98 SE/ME/NT 4.x/2000/2003/XP/Vista/2008 

 
8. Trouble Shooting 

 

Problem 

Probable Cause 

Solution 

The UPS will not 

turn on. 

Battery is disconnected or utility 

power is not available at the wall 

outlet. 

Connect the battery and ensure 

power is available at the wall outlet. 

Yellow LED is 

flashing, and 

alarm is heard 

intermittently. 

But mains is 

normal. 

UPS is not connected properly to 

the mains. 

Connect the UPS according to the 

installation guide. 

Line breaker protected. 

Press the breaker. 

UPS shutdown 

after a few 

seconds and 

circuit breaker 

protected. 

UPS output is short-circuited, 

possibly due to defective 

computer. 

Disconnect your computer from the 

UPS and then press the breaker. 

Inadequate 

runtime 

Battery is not fully charged. 

Charge the unit at least 4 hours. 

Battery is near the end of useful 

life. 

As a battery ages, the amount of 

runtime available will decrease. You 

can replace the battery by following 

the steps above. 

 

 

QUATTRO 600/700/800 Line Interactive UPS

 

User Guide 

Battery backup receptacles area 

with 4 x Schuko, 

Status indicators (Check the 

Status Indicators for the details)

 

AC power input   

Circuit breaker     

Modem/phone/Network   

surge protection   

Power switch 

USB communication port

 

 