MHT258a (Engl.)
9-12
(g) High voltage, overvoltge
•
Touch panel display
•
Detection (example)
The DC intermediate voltage in the amplifier is higher than the upper limit.
•
Cause, check and remedy
(h) Amp heat, amplifier overheat
•
Touch panel display
•
Detection (example)
The temperature of cooling-fins of the amplifier is above 100 [°C]
• Cause, check and remedy
The ambient temperature for the amplifier should be below +55 [°C]
(i) Encoder communication error
•
Touch panel display
•
Detection (example)
The communication is not made between 16-bit serial encoder and amplifier.
•
Cause, check and remedy
The encoder wiring may be detached or disconnected.
The serial communication is performed at 4[Mbps] of data rate. Do not extend the wiring by connecting several short cables.
Connect the encoder by option cable or specified cables.
The encoder wiring has about 5[V] of voltage amplitude. Do no install it in a location where a strong electric or magnetic field exists.
Overvoltage (Hv)
Contact us
Power capacitor is turned ON/OFF
on same line.
Occurs when turning on power.
Power supply voltage may be higher than specified.
Study a use of AC reactor.
Braking resistor is connected.
Study a use of external braking resistor (0.2 [kW] max.).
Braking resistor is free from
disconnect.
Check the resistance of braking resistor.
For resistance of braking resistor, see 10.6.
Summary of Contents for Faldic-a Series
Page 1: ...RYS V Type User s Manual MHT258a Engl...
Page 55: ...3 28 MHT258a Engl 2 RYS amplifier a 0 03 to 0 2 kW 5 5 150 0 5 0 5 53 60 160 130...
Page 56: ...3 29 MHT258a Engl b 0 4 kW 160 130 60 80 53 150 0 5 0 5 5 5...
Page 57: ...3 30 MHT258a Engl c 0 75 kW 130 160 60 100 54 39 0 5 0 5 150 0 5 0 5 5 5...
Page 58: ...3 31 MHT258a Engl d 1 to 1 5 kW 160 130 60 115 54 54 0 5 0 5 150 0 5 0 5 5 5 Cooling fan...