MHT258a (Engl.)
8-6
8.3 Control input signal
Carry out a test running using the control input signals.
Turn off power and connect the control input/output wiring to CN1.
(1) Control input signals
In the monitor mode of the touch panel, control input signal ON/OFF can be checked.
Key input
LC display (example)
Remark
Example of test running mode display
MODE
MODE
MODE
MODE
ESC
ESC
ESC
ESC
The MODE key selects a mode.
MODE
MODE
MODE
MODE
ESC
ESC
ESC
ESC
Select the monitor mode.
By
∧
key or
∨
key, select [On012]
SHIFT
SHIFT
SHIFT
SHIFT
ENT
ENT
ENT
ENT
Holding down the ENT key for at least 1 [sec] allows to check the input
signal ON/OFF.
If a control input signal on CN1 turns ON, the corresponding LED lights.
The input signal display [On012] in the monitor mode is updated in real-time.
Remark : CN1 is not factory assigned to the following signals.
•
Forced stop (10)
•
+OT (7)
•
External fault input (34)
•
-OT (8)
These signals are N.C. (or
“
b
”
) break contact. Connecting the CN1 allows to run the motor.
At the factory set status, the amplifier carried out a speed control.
Assign a position control (37) for position control by pulse train, etc., or a torque control (38) for torque control.
These signals can be validated at all times by assigning the system para. 87 or 88.
[CONT8]・・・・・[CONT3][CONT2][CONT1]
(Position control) [REV] [FWD] [RUN]
Summary of Contents for Faldic-a Series
Page 1: ...RYS V Type User s Manual MHT258a Engl...
Page 55: ...3 28 MHT258a Engl 2 RYS amplifier a 0 03 to 0 2 kW 5 5 150 0 5 0 5 53 60 160 130...
Page 56: ...3 29 MHT258a Engl b 0 4 kW 160 130 60 80 53 150 0 5 0 5 5 5...
Page 57: ...3 30 MHT258a Engl c 0 75 kW 130 160 60 100 54 39 0 5 0 5 150 0 5 0 5 5 5...
Page 58: ...3 31 MHT258a Engl d 1 to 1 5 kW 160 130 60 115 54 54 0 5 0 5 150 0 5 0 5 5 5 Cooling fan...