MHT258a (Engl.)
5-17
・
Pulse train ratio 1, 2
Move amount of mechanical equipment system per 1 pulse of pulse train input can be converted to unit quantity using the command
pulse correction
α
and
β
.
The scale factor ratio to the move amount of mechanical equipment system can also be changed using the pulse train ratio 1 (27) and 2
(28) setting of the control input signals.
Basic parameter 93, 94
Para.
Name
Setting range
Initial value
Change
93
Pulse train ratio 1
0.01 to 100.00 (in 0.01s steps)
1.00
Always
94
Pulse train ratio 2
0.01 to 100.00 (in 0.01s steps)
10.00
Always
Decimal point can be displayed at the current position indication on the keypad panel by the basic para. 95 setting. Mechanical equipment
system position can be checked by the numerical value with decimal point.
Basic parameter 95
Para.
Name
Setting range
Initial value
Change
95
Decimal point at positioning data
0 : 1
1 : 0.1
2 : 0.01
3 : 0.001
4 : 0.0001
5 : 0.00001
0
Always
Manual feed (forward command, reverse command), origin return and interrupt positioning are invalid while the pulse train ratio factor 1 or
2 is on and the pulse train input is effective.
Temporary stop (pause) and positioning cancel signal are invalid when pulse train input is effective.
・
Pulse train input
Position control comes to effective for the following conditions :
Run command [RUN] on
Forced stop [EMG] on
(Control output ready [RDY] on)
Position control (37) on
Pulse train ratio 1 (27) or 2 (28) is already on
Pulse train input is effective.
Summary of Contents for Faldic-a Series
Page 1: ...RYS V Type User s Manual MHT258a Engl...
Page 55: ...3 28 MHT258a Engl 2 RYS amplifier a 0 03 to 0 2 kW 5 5 150 0 5 0 5 53 60 160 130...
Page 56: ...3 29 MHT258a Engl b 0 4 kW 160 130 60 80 53 150 0 5 0 5 5 5...
Page 57: ...3 30 MHT258a Engl c 0 75 kW 130 160 60 100 54 39 0 5 0 5 150 0 5 0 5 5 5...
Page 58: ...3 31 MHT258a Engl d 1 to 1 5 kW 160 130 60 115 54 54 0 5 0 5 150 0 5 0 5 5 5 Cooling fan...