MHT258a (Engl.)
5-27
・
Function of soft OT
When 1 is set at system para.75, the soft OT is able to operate on condition that the current position is bsoft OT and –soft OT
detection position (system para. 77 and 76 setting).
In case the current position goes out of range, stops the motor forcibly, a control output OT detection (20) is turned on. When the pulse
train input with opposite direction to the detection direction is input, or manual feed (forward command/reverse command) is input, and
the current position retruns to within the range, OT detection (20) is turned off, and it allows the mechanical equipment system to move in
both directions.
The soft OT function can be also valid after the origin return complete by basic para. 67 setting.
Basic parameter 67
Para.
Name
Setting range
Initial value
Change
67
Position detection valid/invalid
0: Effective after end of origin return, 1: Always
0
Always
*When the origin return action is completed or the position preset is executed, the origin return is completed.
5.5.4 Torque limit [TLMT], torque limit detection
This function limits the motor output torque.
Motor output torque can be limited while torque limit [TLMT] (30) signal is on.
Torque limit value can be set by basic para. 59, from 0 to maximum output torque in 1% steps.
Maximum output torque depends on motor type.
Maximum output torque is set assuming the rated torque is 100%.
Torque limit is always effective in any control condition.
If output torque is limited during acceleration or deceleration, acceleration or deceleration may not follow the accel./decel. time set by basic
para.
・
Torque limit detection
This signal is turned on while motor torque reaches the torque limit value.
This torque limit detection (26) is effective in all control condition.
■
Interface
−
Soft OT detection position
(system para. 77)
+ Soft OT detection position
(system para. 76)
Current feedback position
Movable zone
Torque limit (30)
ON : The motor output torque is limited to the value set by para. 59.
OFF : The motor can output torque to its max. torque
Torque limit detection (26)
ON : Maximum torque is being output.
OFF : Maximum torque is not output.
P24
M24
2.2k
+24V
+24V
Summary of Contents for Faldic-a Series
Page 1: ...RYS V Type User s Manual MHT258a Engl...
Page 55: ...3 28 MHT258a Engl 2 RYS amplifier a 0 03 to 0 2 kW 5 5 150 0 5 0 5 53 60 160 130...
Page 56: ...3 29 MHT258a Engl b 0 4 kW 160 130 60 80 53 150 0 5 0 5 5 5...
Page 57: ...3 30 MHT258a Engl c 0 75 kW 130 160 60 100 54 39 0 5 0 5 150 0 5 0 5 5 5...
Page 58: ...3 31 MHT258a Engl d 1 to 1 5 kW 160 130 60 115 54 54 0 5 0 5 150 0 5 0 5 5 5 Cooling fan...