MHT258a (Engl.)
6-26
System parameter
The system parameter is used for the function setting of the control input/output terminals of amplifier.
Changed setting of most parameters is effective only after turning off and on power.
■
System parameter for RYS-V type (1/2)
No.
Name
Setting range
Initial value
Change
01
CONT1 signal assignment
0 to 56 (in 1 steps)
1
Power
02
CONT2 signal assignment
0 to 56 (in 1 steps)
2
Power
03
CONT3 signal assignment
0 to 56 (in 1 steps)
3
Power
04
CONT4 signal assignment
0 to 56 (in 1 steps)
11
Power
05
CONT5 signal assignment
0 to 56 (in 1 steps)
51
Power
06
CONT6 signal assignment
0 to 56 (in 1 steps)
52
Power
07
CONT7 signal assignment
0 to 56 (in 1 steps)
27
Power
08
CONT8 signal assignment
0 to 56 (in 1 steps)
37
Power
09
to
21
Unused
−
0
−
22
Parameter RAM storage 1
0: Not assigned 1 to 99: Basic parameter No.
0
Power
23
Parameter RAM storage 2
0: Not assigned 1 to 99: Basic parameter No.
0
Power
24
Parameter RAM storage 3
0: Not assigned 1 to 99: Basic parameter No.
0
Power
25
Parameter RAM storage 4
0: Not assigned 1 to 99: Basic parameter No.
0
Power
26
Parameter RAM storage 5
0: Not assigned 1 to 99: Basic parameter No.
0
Power
27
Parameter RAM storage 6
0: Not assigned 1 to 99: Basic parameter No.
0
Power
28
Parameter RAM storage 7
0: Not assigned 1 to 99: Basic parameter No.
0
Power
29
Parameter RAM storage 8
0: Not assigned 1 to 99: Basic parameter No.
0
Power
30
Parameter RAM storage 9
0: Not assigned 1 to 99: Basic parameter No.
0
Power
31
OUT1 signal assignment
0 to 41 (in 1 steps)
1
Power
32
OUT2 signal assignment
0 to 41 (in 1 steps)
28
Power
33
OUT3 signal assignment
0 to 41 (in 1 steps)
24
Power
34
OUT4 signal assignment
0 to 41 (in 1 steps)
0
Power
35
OUT5 signal assignment
0 to 41 (in 1 steps)
0
Power
Function (Input signal) number assigned to
system para.1 to 8 (CONT1 to CONT8)
Function (Output signal) assigned to
system para.31 to 35 (OUT1 to OUT5)
0: Not assigned
37: Position control
0: Not specified
32: Alarm code 0
1: Run command [RUN]
38: Torque control
1: Ready [RDY]
33: Alarm code 1
2: Forward command [FWD]
43: Override valid
2: Positioning end [PSET]
34: Alarm code 2
3: Reverse command [REV]
44: Override1
14: Brake timing
35: Alarm code 3
5: Origin return [ORG]
45: Override2
15: Dynamic braking
36: Alarm code 4
6: Origin LS [LS]
46: Override4
16: Alarm detection [ALM]
38: +OT detection
7: +OT
47: Override8
17: Fixed, passing point 1
39: -OT detection
8: -OT
48: Interrupt input valid
18: Fixed, passing point 2
40: Origin LS detection
10: Forced stop [EMG]
49: Interrupt input
20: OT detection
41: Forced stop detection
11: Alarm reset [RST]
50: Deviation clear
22: Origin return end
14: ACC0
51: X1
23: Deviation zero
16: Position preset
52: X2
24: Speed zero [NZERO]
27: Pulse train ratio 1
53: X3
25: Speed arrive [NARV]
28: Pulse train ratio 2
54: Free-run [BX]
26: Torque limit detection
29: P-action
55: Edit permit command
27: Overload early warning
30: Torque limit
56: Current position output
28: CPU ready [CPURDY]
34: External fault input
29: Edit permit on
31: Address error
Summary of Contents for Faldic-a Series
Page 1: ...RYS V Type User s Manual MHT258a Engl...
Page 55: ...3 28 MHT258a Engl 2 RYS amplifier a 0 03 to 0 2 kW 5 5 150 0 5 0 5 53 60 160 130...
Page 56: ...3 29 MHT258a Engl b 0 4 kW 160 130 60 80 53 150 0 5 0 5 5 5...
Page 57: ...3 30 MHT258a Engl c 0 75 kW 130 160 60 100 54 39 0 5 0 5 150 0 5 0 5 5 5...
Page 58: ...3 31 MHT258a Engl d 1 to 1 5 kW 160 130 60 115 54 54 0 5 0 5 150 0 5 0 5 5 5 Cooling fan...