FR200 Series Vector control inverter
- 90 -
deceleration time
selection
19
Acceleration/Decele
ration
prohibited
When "Accel/Decel disabled" terminal is enabled, the drive
maintains the present output frequency and no longer
responds to the change of command frequency. But it will
still perform ramp-down stop when receiving stop command.
This terminal is disabled during normal ramp-down stop.
20
Switch to auxiliary
frequency source
setting
Switch integrated frequency source setting mode to auxiliary
frequency source setting mode.
21
PLC status reset
When simple PLC is running and this terminal is enabled. The
status (running time and step) of PLC will be cleared and the
output frequency is step 0. When this terminal is disabled
again, the drive resumes PLC running from step 0.
22
Simple PLC paused
When simple PLC is running and this terminal is enabled, the
current PLC status (running time and step) will be memorized,
and the drive will run at 0Hz. When this terminal is disabled,
the drive restores its running from the memorized moment.
23
PID pause
When this terminal is enabled, PID adjustment is paused, and
the drive will maintain current output frequency. After this
terminal becomes disabled, PID adjustment recovers.
24
Reverse PID action
direction
After this terminal becomes ON, the PID action direction is
reversed to the direction set in F13.04.
25
PID integral pause
After this terminal becomes ON, the integral adjustment
function pauses. However, the proportional and differentiation
adjustment functions are still valid.
26
PID parameter
switchover
When PID parameter switch is set to "2: switched by terminal",
this terminal could be used to realize the switching between
two groups of PID parameters. When this terminal is enabled,
PID parameters are Kp1 and Ti1, Td1.
When this terminal is disabled, PID parameters are Kp2, Ti2
and Td2.
27
Swing frequency
pause(output the
current frequenc)
The AC drive outputs the current frequency, and the swing
frequency function pauses.
28
Swing frequency
reset(output the
central frequency)
The AC drive outputs the central frequency, and the swing
frequency function pauses.
29
Run comman
switched to keypad
control
This terminal should be enabled by trigger edge. When this
terminal status is switched from OFF to ON, run command will
be switched to keypad control.
30
Run comman
switched to terminal
control
This terminal should be enabled by trigger edge. When this
terminal status is switched from OFF to ON, run command will
be switched to terminal control.
31
Run comman
switched to
communication
control
This terminal should be enabled by trigger edge. When this
terminal is switched from OFF to ON, run command will be
switched to communication control.
32
Count input
The maximum frequency at count pulse input terminal is
200Hz, and the count value can be memorized in case of
power loss. With the setting of F14.07 (set count value) and
14.08 (designated count value), this terminal can control
digital output "set count value attained" and "designated count
value attained".
33
Count clear
Used with "count input" terminal, to clear pulse count value.
34
Length count
It is used for fixed-length control, and only takes effect on
digital input terminal DI7/HI. The length is calculated via
pulse input. Please refer to specification of parameters