FR200 Series Vector control inverter
- 96 -
detection FDT2 output
5
Drive in 0Hz running
1(no output at stop)
When be running at 0Hz, this corresponding terminal
outputs ON signal. No ON signal will be output at stop.
6
Drive in 0Hz running
2(output at stop)
Outputs ON signal when is running at 0Hz and also outputs
ON signal at stop.
7
Upper limit frequency
attained
When output frequency attains F01.09 (upper limit
frequency), outputs ON.
8
Lower limit frequency
attained (no output at
stop)
When output frequency attains F01.10 (lower limit
frequency), outputs ON. In the stop state, the terminal
becomes OFF.
9
Frequency attained
Refer to the descriptions of F05.09.
10
Ready for RUN
If the AC drive main circuit and control circuit become
stable, and the AC drive detects no fault and is ready for
RUN, the terminal becomes ON.
11
Drive (motor)
overloaded alarm
In case drive output current exceeds F11.19 (overload
alarm threshold) and its last time exceeds F11.20 (overload
alarm activated time that exceeding threshold), outputs ON.
Refer to parameters F11.18
~
F11.20 for information with
regard to drive (motor) overloaded alarm.
12
Drive overheat alarm
When drive internally detected temperature exceeds F11.21
(Drive overheat alarm threshold), ON signal will be output.
13
Current running time
attained
When current running time attains the value of F05.14,
corresponding terminal outputs ON. Current running time is
cleared when stop.
14
Accumulative
power-on time
attained
When accumulative power-on time attains the value of
F05.15, corresponding terminal outputs ON. Accumulative
power-on time is maintained when stop.
15
Accumulative running
time attained
When accumulative running time attains the value of
F05.16, corresponding terminal outputs ON. Accumulative
running time is maintained when stop.
16
PLC cycle completed
Upon the completion of a cycle of simple PLC running, ON
signal with a width of 250ms will be output.
17
Set count value
attained
The terminal becomes ON when the count value reaches
the value set in F14.07.
18
Designated count
value attained
The terminal becomes ON when the count value reaches
the value set in F14.08. Refer to the specification of
parameter F14.07 and F14.08.
19
Length attained
The terminal becomes ON when the detected actual length
exceeds the value set in F14.04. Refer to the specification
of parameter F14.05
~
F14.07.
20
Under load alarm
When inverter under load, output ON signal
21
Brake Output
When the brake function selection is effective and reach
brake open condition, output signal ON
22
~
99
Reserved
F05.04
Y1 output delay time
Range:0.0
~
6000.0s
Default:0.0s
F05.05
Y2 output delay time
Range:0.0
~
6000.0s
Default:0.0s
F05.06
Relay 1 output delay time
Range:0.0
~
6000.0s
Default:0.0s
F05.07
Relay 2 output delay time
Range:0.0
~
6000.0s
Default:0.0s
These four parameters define the delay response time of digital output terminals Y1 & Y2, relay 1
and relay 2.
F05.08
Enabled state of digital
output
Range:0000
~
1111
Default:0000
Unit's place: Y1
0: Positive logic; ON when current passes through