FR200 Series Vector control inverter
- 92 -
Acceleration/Deceler
ation time
determinant 2
Acceleration/Deceler
ation time
determinant 1
Acceleration/Deceleratio
n Time Selection
Corresponding
Parameters
OFF
OFF
Acceleration/Deceleratio
n time 1
F03.00
、
F03.01
OFF
ON
Acceleration/Deceleratio
n time 2
F03.02
、
F03.03
ON
OFF
Acceleration/Deceleratio
n time 3
F03.04
、
F03.05
ON
ON
Acceleration/Deceleratio
n time 4
F03.06
、
F03.07
F04.10
Filtering time of digital
input terminal
Range:0.000
~
1.000s
Default:0.010s
Set the filtering time of DI1
~
DI7 (when DI7/HI is used as ordinary low-speed terminal), AI1, AI2
and AI3 (when used as digital input terminal). Interference immunity of digital input terminals can be
improved by appropriate filtering time. However, the response time of digital input terminal will become
slower when filtering time is increased.
ATTENTION:
This filtering time takes no effect on DI7/HI when DI7/HI terminal is used as DI high-speed input
terminal, while the filtering time of DI is determined by parameter F06.36.
F04.11
Delay time of terminal DI1
Range:0.0
~
300.0s
Default:0.0s
F04.12
Delay time of terminal DI2
Range:0.0
~
300.0s
Default:0.0s
The delayed response time of digital input terminals DI1 and DI2 is set by these two parameters.
ATTENTION:
Terminal delay time F04.11and F04.12 can be set with filtering time F04.10 at the same time. The
drive will respond after the signals via DI1 and DI2 go through filtering time, and then delay time.
Terminals DI3
~
DI7 have no delay time function.
F04.13
Terminal DI1
~
DI5
positive/negative logic
Range:00000
~
11111
Default:00000
These parameters are used to set the valid mode of DI terminals.
Unit's place: DI1
0: Positive logic
The DI terminal is valid when being connected with COM, and invalid when being disconnected
from COM.
1: Negative Logic
The DI terminal is invalid when being connected with COM, and invalid when being disconnected
from COM.
Ten's digit: DI2 (same as DI1)
Hundred's digit: DI3 (same as DI1)
Thousand's digit: DI4 (same as DI1)
Ten thousand's digit: DI5 (same as DI1)
F04.14
Terminal DI6
~
AI3
positive/negative logic
Range:00000
~
11111
Default:00000
Unit's place: DI6
0: Positive logic
The DI terminal is valid when being connected with COM, and invalid when being disconnected
from COM.
1: Negative Logic
The DI terminal is invalid when being connected with COM, and invalid when being disconnected
from COM.
Ten's digit: DI7 (same as DI6)
Hundred's digit: AI1
0: Positive logic ;< 3V, valid; > 7V, invalid