FR200 Series Vector control inverter
- 123 -
frequency
~
Fmax
F14.11
Wake up delay time
Range
:
0.0
~
6000.0s
Default
:
0.0s
F14.12
Dormancy frequency
Range
:
0.00
~
Wake up
frequency
Default
:
0.00Hz
F14.13
Dormancy delay time
Range
:
0.0
~
6000.0s
Default
:
0.0s
F14.17
Wake up pressure
Range
:
0.0%
~
Dormancy
pressure
Default
:
10.0%
F14.18
Dormancy pressure
Range
:
Wake
up
pressure
~
100.0%
Default
:
50.0%
The parameters are used for the dormancy and wake up function in water supply application
During inverter operation, when F14.15 set to be “0”, and when setting frequency is lower than
F14.12, after delay time of F14.13, inverter entry dormancy and stop. When F14.15 set to be “1”, and
when pressure feedback is bigger than F14.18, after delay time of F14.13, inverter entry dormancy
and stop
During inverter dormancy, when F14.14 set to be “0”, and when setting frequency is bigger than
F14.10, after delay time of F14.11, inverter start to operate; When F14.14 set to be “1”, and when
pressure feedback is lower than F14.17, after delay time of F14.11, inverter start to operate
Usually, please set wake up frequency bigger than dormancy frequency. If wake up frequency and
dormancy frequency are set to be 0.00Hz, wake up and dormancy function is invalid.
When start dormancy function, if frequency source is PID, need to set F13.26 to be “1” PID
operation at stop
F14.14
Wake up mode selection
Range
:
0
~
1
Default
:
0
0
:
Frequency
When inverter in dormancy, wake up mode is frequency wake up
1
:
Pressure
When inverter in dormancy, wake up mode is pressure wake up
F14.15
Dormancy mode selection
Range
:
0
~
1
Default
:
0
0
:
Frequency
Inverter dormancy mode is frequency dormancy
1
:
Pressure
Inverter dormancy mode is pressure dormancy
F14.16
Pressure feedback source
Range
:
0
~
3
Default
:
0
When voltage dormancy or wake up:
0
:
AI1
Pressure feedback given by AI1
1
:
AI2
Pressure feedback given by AI2
2
:
DI7/HI pulse input
Pressure feedback given by DI7/HI
3
:
AI3
Pressure feedback given by AI3
Group F15 Communication Parameters
F15.00
Baud rate
Range:0
~
5
Default:1
0
:
4800bps 1
:
9600bps
2
:
19200bps 3
:
38400bps
4
:
57600bps 5
:
115200bps
F15.01
Data format
Range:0
~
3
Default:0
0: No check, data format (1-8-N-2) for RTU
1: Even parity check, data format (1-8-E-1) for RTU
2: Odd Parity check, data format (1-8-O-1) for RTU
3: No check, data format (1-8-N-1) for RTU
F15.02
Local address
Range:1
~
247
Default:1
Set this drive address. 0 is broadcast address, while available addresses are 1
~
247.
F15.03
Communication timeout
Range:0.0
~
60.0s
Default:0.0s