FR200 Series Vector control inverter
- 102 -
Curve AI2 is defined by F06.08
~
F06.15. Curve AI3 is defined by F06.16
~
F06.23. The usage of
curve AI2 and curve AI3 is the same as that of curve AI1.
F06.24
Minimum input of curve
keypad potentiometer
Range:0.0
~
Maximum input of
curve keypad potentiometer
Default:0.0%
F06.25
Set value corresponding to
minimum input of curve
keypad potentiometer
Range:-100.0
~
100.0%
Default:0.0%
F06.26
Maximum input of curve
keypad potentiometer
Range: Minimum input of curve
keypad potentiometer
~
100.0%
Default:100.0%
F06.27
Set value corresponding to
maximum input of curve
keypad potentiometer
Range:-100.0
~
100.0%
Default:100.0%
Curve keypad potentiometer is defined by above-noted 4 parameters.
Input values F06.24
、
F06.26:
keypad potentiometer is 0
~
5V on control board. 0V corresponds to 0%, while 5V corresponds to
100%.
Corresponding set values F06.25
、
F06.27:
When the corresponding set value is frequency: 100% is the maximum frequency, while -100% is
the maximum negative frequency.
When corresponding set value is torque: 100% means 2 times the rated torque, while -100%
means negative "2 times the rated torque".
When the corresponding set value is output voltage (e.g. the voltage setting in case of V/f
separated pattern): 100% corresponds to rated voltage of motor. "Less than or equal to 0%"
corresponds to 0V voltage. The difference is thatcurve keypad potentiometer is a straight line while
curve AI1
~
AI3 is a broken line with two inflection points.
F06.28
AI1 terminal filtering time
Range:0.000
~
10.000s
Default:0.100s
F06.29
AI2 terminal filtering time
Range:0.000
~
10.000s
Default:0.100s
F06.30
AI3 terminal filtering time
Range:0.000
~
10.000s
Default:0.100s
F06.31
Keypad potentiometer
filtering time
Range:0.000
~
10.000s
Default:0.100s
F06.28
~
F06.31 define the filtering time of analog input terminals AI1, AI2 , AI3 and Keypad
potentiometer. Long filtering time results in strong immunity from interference but slow response, while
short filtering time brings rapid response but weak immunity from interference.
F06.32
Minimum input of curve HI
Range:0.00kHz
~
Maximum
input of curve HI
Default:0.00kHz
F06.33
Set value corresponding to
minimum input of curve HI
Range:-100.0
~
100.0%
Default:0.0%
F06.34
Maximum input of curve HI
Range: Minimum input of
curve HI
~
100.00kHz
Default:100.00kHz
F06.35
Set value corresponding to
maximum input of curve HI
Range:-100.0
~
100.0%
Default:100.0%
Curve HI is defined by above-noted 4 parameters.
Input values F06.32
、
F06.34:
HI is 0
~
100kHz.
Corresponding set values F06.33
、
F06.35:
When the corresponding set value is frequency: 100% is the maximum frequency, while -100% is
the maximum negative frequency.
When corresponding set value is torque: 100% means 2 times the rated torque, while -100%
means negative "2 times the rated torque".
When the corresponding set value is output voltage (e.g. the voltage setting in case of V/f
separated pattern): 100% corresponds to rated voltage of motor. "Less than or equal to 0%"
corresponds to 0V voltage.
ATTENTION:
When pulse input is selected as the frequency command, DI7/HI terminal shall be set to "pulse
input" function (F00.09 is set to 1).
F06.36
HI terminal filtering time
Range:0.000
~
10.000s
Default:0.100s