FR200 Series Vector control inverter
- 47 -
Fig.3-26 4.0
~
15kW RFI jumper schematic
75
~
132KW jumper method: Terminal plug is jumped state, unplug the state is not jumper
RFI jumper after RFI jumper before
Fig 3-27 37
~
75kW Short-circuit diagram
ATTENTION:
1. When power is applied to the AC motor drive, do not cut off the RFI jumper.
2. Make sure main power is switched off before cutting the RFI jumper.
3. The gap discharge may occur when the transient voltage is higher than 1,000V. Besides, electro-magnetic
compatibility of the AC motor drives will be lower after cutting the RFI jumper.
4. Do NOT cut the RFI jumper when main power is connected to earth.
5. The RFI jumper cannot be cut when Hi-pot tests are performed. The mains power and motor must be
separated if high voltage test is performed and the leakage currents are too high.
6. To prevent drive damage, the RFI jumper connected to ground shall be cut off if the AC motor drive is installed
on an ungrounded power system or a high resistance-grounded (over 30 ohms) power system or a corner grounded
TN system.