FR200 Series Vector control inverter
- 27 -
Chapter 3 Installation and Wiring
3.1 Installation Environment
1
)
Ambient temperature in the range of -10
℃~
50
℃
.
2
)
Drive should be installed on surface of flame retardant object, with adequate surrounding space for
heat dissipation.
3
)
Installation should be performed where vibration is less than 5.9m/s2 (0.6g).
4
)
Avoid from moisture and direct sunlight.
5
)
Protect the cooling fan by avoiding oil, dust and metal particles;
6
)
Do not expose to an atmosphere with flammable gases, corrosive gases, explosive gases or other
harmful gases.
7
)
Prevent drilling residues, wire ends and screws falling into drive.
8) Ventilation part of the drive should be installed outside from harsh environment (e.g. Textile facilities
with fiber particles and chemical facilities filled with corrosive gases or Loaded dust cover).
3.2 Installation Direction, Space and Cooling
A fan is integrated in FR200 for forced air cooling. FR200 has to be installed vertically for the purpose
of good cooling circulation. Sufficient spaces have to be left between FR200 and its peripheral objects.
Multi- FR200 can be installed in parallel horizontally e and vertically. See followings for specific space
requirement, heat dissipating capacity and mass airflow.
FR200 series inverter installation of the following three
:
Wall mounting
:
(
suitable for 400KW (inclusive)
)
.
Wall-mounted
:
(
suitable for 132KW (inclusive)
)
.
Remark
:
0.75
~
15kW need to install an optional foot hanging
;
18.5
~
132kW do not need to install an optional foot
hanging.
Floor installation
:(
Suitable for 90-630kW inverter
)
.
The wall mount
Through wall-mounted
Fig 3-1 Installation methods