FR200 Series Vector control inverter
- 46 -
+5V
24V
+24V
Y1,2
COM
Relays
FR200
Optocoupler
+5V
24V
+24V
Y1,2
COM
Relays
FR200
+-
≤
30V
Optocoupler
(a) Internal power supply
(
b
)
External power supply
Fig 3-25 mode of connection when the terminal drives relay
ATTENTION:
When relay coil voltage is lower than 24V, a resistor as voltage divider should be mounted between
relay and output terminal, based on coil impedance.
4
)
Wiring instruction of relay output terminal
Control boards of FR200 series drives are provided with two programmable relay dry contact outputs.
One relay contacts are R1A/R1B/R1C, whose R1Aand R1C are normally open, while R1B and R1C
are normally closed. See parameter F05.02 for details.
The others contacts are R2A /R2B/R2C, whose R2A and R2C are normally open, while R2B and R2C
are normally closed. See parameter F05.03 for details.
ATTENTION:
In case inductive load (e.g. electromagnetic relay or contactor) is to be driven, a surge voltage
absorbing circuit such as RC absorbing circuit (note that its leakage current shall be less than holding
current of controlled contactor or relay), piezoresistor or fly-wheel diode etc. shall be mounted (be sure
to pay close attention to polarity in case of DC electromagnetic circuit). Absorbing devices should be
mounted close to the ends of relay or contactor.
5) Instruction of Signal Switch
AI1
V
I
AI2
V
I
AO1
V
I
AO2
V
I
485
ON
OFF
Terminal
Function
Factory
default
AI1
I: current input (0
~
20mA); V: voltage input (0
~
10V)
0
~
10V
AI2
I: current input (0
~
20mA); V: voltage input (0
~
10V)
0
~
10V
AO1
I: current output (0
~
20mA); V: voltage output (0
~
10V)
0
~
10V
AO2
I: current output (0
~
20mA); V: voltage output (0
~
10V)
0
~
10V
RS485
Selection of
485 termination resistor; ON :120Ω termination
resistor provided; OFF: no termination resistor
No
termination
resistor
3.8.3 RFI Short wiring instructions
If the AC motor drive is supplied from an isolated power (IT power), the RFI jumper must be cut off.
Then the RFI capacities (filter capacitors) will be disconnected from ground to prevent circuit damage
(according to IEC 61800-3) and reduce earth leakage current.
4.0
~
15kW RFI jumper method: Screw matter is jumped state, release is not jumped state