FR200 Series Vector control inverter
- 137 -
name
Description
Function Code
(F00.00
~
U01.99)
High byte function code group number, F00
~
F31, U00, U01,
respectively, corresponding to the high byte address is 00H
~
1FH, 30H,
31H.
Low byte of the group function code number, from 0 to 99 corresponding
to the low byte address is 00H
~
63H.
For example: Modify F01.02 function code value, no power-down when
storing the corresponding register address (referred to as RAM address)
to 0102H.
EEPROM is frequently modified, will reduce the life of the EEPROM. If
you modify the value of the function code-down storage needs, you can
make this function code is the highest position a high address. Note that
this address is only to write, not read.
For example: Modify F01.02 function code value, and the corresponding
need to power down when storing the register address (referred to as
EEPROM address) to 8102H.
Function code group
RAM address high byte
EEPROM address high byte
F00
0x00
0x80
F01
0x01
0x81
F02
0x02
0x82
……
……
……
F30
0x1E
0x9E
F31
0x1F
0x9F
U00 (Read Only)
0x30
--
U01 (Read Only)
0x31
--
4.4 Address and control command functions: (write only)
Command word address
Command Function
2000H
0001: Forward run
0002: Reverse Run
0003: Inching Forward
0004: Reverse Jog
0005: Slowdown stop
0006: freewheel
0007: Fault reset
2001H
Communication setting frequency (0
~
Fmax (Unit: 0.01Hz))
2002H
PID given range (0 to 1000, 1000 corresponds to 100.0%)
2003H
PID feedback range (0
~
1000, 1000 corresponds to 100.0%)
2004H
Torque set point (-3000
~
3000, 1000 corresponds to 100.0%
motor rated current)
2005
~
20FF
Retention