FR200 Series Vector control inverter
- 42 -
◆
The capacitor or surge absorber cannot be connected to the output side of the AC drive. Otherwise,
it may cause frequent AC drive fault or even damage the AC drive.
If the motor cable is too long, electrical resonance will be generated due to the impact of distributed
capacitance. This will damage the motor insulation or generate higher leakage current, causing the AC
drive to trip in overcurrent protection. If the motor cable is greater than 100 m long, an AC output
reactor must be installed close to the AC drive.
5
)
Terminal
PE
◆
This terminal must be reliably connected to the main earthing conductor. Otherwise, it may cause
electric shock, mal-function or even damage to the AC drive.
◆
Do not connect the earthing terminal to the neutral conductor of the power supply.
3.8.2
Control circuit terminals
D I 1
+24V
DI2
PLC
DI3
COM
DI4
DI5
COM
DI6
Y1
Y2
+10V
R1A R1B R1C
R2A R2B R2C
AO1
AI1
GND
AI2
485+
AI3
485-
PE
DI7/HI
AO2
GND
Fig.3-19 Control circuit terminals
Table 3-7 FR200
Description of control circuit terminals
Type
Terminal
Name
Function Description
Power supply
+10V-GND
Ex10 V
power supply
P10 V power supply to
external unit.
Generally, it provides power supply to
external potentiometer with resistance
range of 1
–5 kΩ.
Maximum output current: 10 mA
+24V-COM
Ex24V
power
supply Applying
to Overvoltage
Category II
circuit
P24 V power supply to
external unit.
Generally, it provides power supply to
DI/Do terminals and external sensors.
Maximum output current: 200 mA
PLC
Input terminal
of
external power
supply
Connect to +24 V by default.
When DI1-DI7 need to be driven by
external signal, PLC needs to be
connected to external power supply
and be disconnected from +24 V.
Analog input
AI1-GND
Analog input 1
Input voltage range
:
DC 0
~
10V/0
~
20mA
,
decided by toggle switches
AI1
、
AI2 on the control board
Impedance: 250 kΩ (voltage input),
250 Ω (current input)
AI2-GND
Analog input 2
AI3-GND
Analog input 3
Input Voltage Range
:
DC -10
~
+10V
Input impedance
:
250kΩ
Switch input
DI1- COM
Switch input
terminals 1
Maximum input frequency
:
200Hz
Impedance
:
2.4kΩ
Voltage range for level input
:
9V
~
30V
DI2- COM
Switch input
terminals 2
DI3- COM
Switch input
terminals 3
DI4- COM
Switch input
terminals 4