FR200 Series Vector control inverter
- 64 -
F07.01
AO2 output function
1: Output frequency
2: Command frequency
3: Output current
4: Output voltage
5: Output power
6: Bus voltage
7
:
+10V
8: keypad potentiometer
9:AI1
10:AI2
11:AI3
12:HI
13: Output torque
2
×
F07.02
Y2/HO output function
(when used as HO)
1
×
F07.03
AO1 offset
-100.0
~
100.0%
0.0%
△
F07.04
AO1 gain
-2.000
~
2.000
1.000
△
F07.05
AO1 filtering time
0.000
~
10.000s
0.000s
△
F07.06
AO2 offset
-100.0
~
100.0%
0.00%
△
F07.07
AO2 gain
-2.000
~
2.000
1.000
△
F07.08
AO2 filtering time
0.000
~
10.000s
0.000s
△
F07.09
HO maximum output
pulse frequency
0.01
~
100.00kHz
50.00kHz
△
F07.10
HO output filtering time
0.000
~
10.000s
0.010s
△
Group F08 Parameters of Motor 1
F08.01
Power rating of motor 1
0.1
~
1000.0kW
Model
defined
×
F08.02
Rated voltage of motor 1
60
~
660V
Model
defined
×
F08.03
Rated current of motor 1
0.1
~
1500.0A
Model
defined
×
F08.04
Rated frequency of
motor 1
20.00
~
Fmax
Model
defined
×
F08.05
Rated speed of motor 1
1
~
30000
Model
defined
×
F08.08
Stator resistance R1 of
async motor 1
0.001
~
65.535Ω
Model
defined
×
F08.09
Rotor resistance R2 of
async motor 1
0.001
~
65.535Ω
Model
defined
×
F08.10
Leakage inductance L1
of async motor 1
0.01
~
655.35mH
Model
defined
×
F08.11
Mutual inductance L2 of
asynchronous motor 1
0.1
~
6553.5mH
Model
defined
×
F08.12
No-load current of
async motor 1
0.1
~
1500.0A
Model
defined
×
F08.13
Field weakening coeff 1
of async motor 1
0.0
~
100.0
87%
×
F08.14
Field weakening coeff 2
of async motor 1
0.0
~
100.0
75%
×
F08.15
Field weakening coeff 3
of async motor 1
0.0
~
100.0
70%
×
F08.30
Autotuning of motor 1
0: No autotuning
0
×
1: Static autotuning of async motor
2: Rotary autotuning of async
motor
Group F09 V/f Control Parameters of Motor 1
F09.00
V/f curve setting
0: Linear V/f
0
×
1: Multi-stage V/f