FR200 Series Vector control inverter
- 109 -
F10.07
ASR input filtering time
Range:0.0
~
500.0ms
Default:0.3ms
F10.08
ASR output filtering time
Range:0.0
~
500.0ms
Default:0.3ms
Sets the input/output filtering time of ASR.No need to modify its default setting if not have special
requirement.
F10.09
Vector control slip gain
Range:50
~
200%
Default:100%
For SFVC, it is used to adjust speed stability accuracy of the motor. When the motor with load
runs at a very low speed, increase the value of this parameter; when the motor with load runs at a very
large speed, decrease the value of this parameter.
For CLVC, it is used to adjust the output current of the AC drive with same load.
F10.10
Digital setting of torque upper
limit in speed control mode
Range:50.0
~
200.0%
Default:100%
In the speed control mode, the maximum output torque of the AC drive is restricted by F10.10.
F10.11
Excitation adjustment
proportional gain Kp1
Range:0.00
~
10.00
Default:0.50
F10.12
Excitation adjustment integral
gain Ti1
Range:0.0
~
3000.0ms
Default:10.0ms
F10.13
Torque adjustment
proportional gain Kp2
Range:0.00
~
10.00
Default:0.50
F10.14
Torque adjustment integral
gain Ti2
Range:0.0
~
3000.0ms
Default:10.0ms
These are current loop PI parameters for vector control. These parameters are automatically
obtained through "Asynchronous motor complete auto-tuning" or "Synchronous motor no-load
auto-tuning", and need not be modified.
F10.16
Torque setting source under
torque control
Range:0
~
6
Default:0
F10.17
Digital setting of torque
Range:-200
~
200%
Default:150.0%
F10.16 is used to set the torque setting source. There are a total of 6 torque setting sources.
The torque setting is a relative value. 100.0% corresponds to the AC drives rated torque. The
setting range is -200.0% to 200.0%, indicating the AC drive's maximum torque is twice of the AC
drive's rated torque.
If the torque setting is positive, the AC drive rotates in forward direction. If the torque setting is
negative, the AC drive rotates in reverse direction.
0: Digital setting (F10.17)
The target torque directly uses the value set in F10.17.
1: Keypad potentiometer
2: AI1
3: AI2
4: AI3
The target torque is decided by analog input.
5: Pulse setting (DI7/HI)
The target torque is set by DI7/HI (high-speed pulse). The pulse setting signal specification is
9
–30 V (voltage range) and 0–100 kHz (frequency range). The pulse can only be input via DI7.
6: Communication setting
The target torque is set by means of communication.
F10.18
Forward speed limited value
under torque control
Range:0.0
~
Fmax
Default:50.0Hz
F10.19
Reverse speed limited value
under torque control
Range:0.0
~
Fmax
Default:50.0Hz
When F00.26=0,Two parameters are used to set the maximum frequency in forward or reverse
rotation in torque control mode.
In torque control, if the load torque is smaller than the motor output torque, the motor's rotational
speed will rise continuously. To avoid runaway of the mechanical system, the motor maximum rotating
speed must be limited in torque control.
You can implement continuous change of the maximum frequency in torque control dynamically
by controlling the frequency upper limit.