FR200 Series Vector control inverter
- 100 -
F06.05
Set value corresponding
to input of inflection
point 2 of curve AI1
Range:-100.0
~
100.0%
Default:75.0%
F06.06
Maximum input of curve
AI1
Range:Input of inflection point
2 of curve AI1
~
100.0%
Default:100.0%
F06.07
Set value corresponding to
maximum input of curve AI1
Range:-100.0
~
100.0%
Default:100.0%
Curve AI1 is defined by above-noted 8 parameters.
Input values F06.00
、
F06.02
、
F06.04
、
F06.06:
AI1
~
AI2 are 0
~
10V or 0
~
20mA programmable by jumper on control board.
If 0
~
10V is selected: 0V corresponds to 0%, while 10V corresponds to 100%.
If 0
~
20mA is selected: 0mA corresponds to 0%, while 20mA corresponds to 100%.
AI3 only supports -10V
~
10V input; For AI3, -10V corresponds to -100%, while 10V corresponds
to 100%.
Corresponding set values F06.01
、
F06.03
、
F06.05
、
F06.07:
When the corresponding set value is frequency: 100% is the maximum frequency, while
-100% is the maximum negative frequency.
When corresponding set value is torque: 100% means 2 times the rated torque, while -100%
Means negative "2 times the rated torque".
When the corresponding set value is output voltage (e.g. the voltage setting in case of V/f
separated pattern): 100% corresponds to rated voltage of motor. "Less than or equal to 0%"
corresponds to 0V voltage.
Curve diagram is shown as below:
For Instance:
Following description is taken AI1 as the example.
(1)
Parameter setting
Table 6-3(1) Parameter setting 1 T able 6-3(2) Parameter setting 2
Code
Value
Code
Value
F06.01
-100
%
F06.00
0.0%
F06.03
-50%
F06.02
25.0%
F06.05
70%
F06.04
75.0%
F06.07
100
%
F06.06
100.0
%
Code
Value
Code
Value
F06.01
100%
F06.00
0%
F06.03
70%
F06.02
40%
F06.05
-50%
F06.04
75%
F06.07
-100%
F06.06
100
%
See Figure 6-15 (1) and Figure 6-15 (2) for input/output bias of Table 6-3(1) and Table 6-3(2)
respectively.
0.0%
25%
75%
100%
-100%
-50%
70%
100%
Fmax
7.5V
10V
F06.01
F06.03
F06.05
F06.07
F06.00
F06.02
F06.04
F06.06
2.5V
Set frequency
Analog input
Figure 6-16 (1)