FR200 Series Vector control inverter
- 83 -
Master frequency command is determined by analog input AI2.
9
:
AI3
Master frequency command is determined by analog input AI3.
F01.02
Digital setting of master
frequency
Range:0.00
~
FmaxHz
Default:0.00Hz
When master frequency source selection F01.01 is set to 1, this parameter value will be the initial
value of master frequency command.
F01.03
Auxiliary frequency command
source
Range:0
~
9
Default: 0
0: Digital setting (F01.04)
When the inverter is powered on, the value of F01.02 is taken as the master frequency source.
1: Keypad potentiometer
Auxiliary frequency command is determined by keypad potentiometer.
2: Analog input AI1
Auxiliary frequency command is determined by analog input AI1.
3: Communication
Upper computer is the auxiliary frequency command source of the drive through standard RS485
communication interface on the drive.
4: Multi-reference
Auxiliary frequency command is determined by multi-reference. See parameter Group F04 for
details.
5: PLC
Auxiliary frequency command is determined by simple PLC. See parameter Group F12 for details.
6: Process PID output
Auxiliary frequency command is determined by process PID computation result. See parameter
Group F13 for details.
7: DI7/HI pulse input
Auxiliary frequency command is determined by DI7/HI pulse input.
8
:
AI2
Auxiliary frequency command is determined by analog input AI2.
9
:
AI3
Auxiliary frequency command is determined by analog input AI3.
F01.04
Digital setting of auxiliary
frequency
Range:0.00
~
Fmax
Default:0.00Hz
When auxiliary frequency command F01.03 is set to 0, this parameter value should be the initial
value of auxiliary frequency command.
F01.05
Range of auxiliary frequency
Range:0
~
1
Default: 0
0: Relative to maximum frequency
1: Relative to master frequency
See F01.06 specification for details.
F01.06
Coeff of auxiliary frequency
Range:0.0
~
150.0%
Default:100.0%
F01.05 and F01.06 will determine the final output value of auxiliary frequency command.
When F01.05 is set to 0 (relative to maximum frequency):
The auxiliary frequency= the auxiliary freq
When F01.05 is set to 1 (relative to master frequency):
The setting range of the auxiliary frequency varies according to the master frequency.
F01.07
Jog frequency
Range:0.00
~
Fmax
Default:5.00Hz
This parameter sets the running frequency during jog.
F01.08
Maximum frequency
Range:20.00
~
600.00
Default:50.00Hz
Maximum frequency of F01.08 is the maximum allowable output frequency of drive.
F01.09
Upper limit frequency
Range:Fdown
~
Fmax
Default:50.00Hz
F01.10
Lower limit frequency
Range:0.00
~
Fup
Default:50.00Hz
F01.09upper limit frequency is the user-defined maximum allowable running frequency; F01.10
lower limit frequency is user-defined minimum allowable running frequency.
ATTENTION: