FR200 Series Vector control inverter
- 35 -
Output filter
Output filter and radiated interference of the drive to
peripheral devices
Output AC
reactor
Avoid the motor insulation damage result from
harmonic voltage Reduce frequent protection from the
drive caused by leakage current In case the cable
connecting drive and motor is over 100 meters, output
AC reactor recommended
3.6.1 Selection of Peripheral Devices
Table 3-3 Selection of peripheral devices
Model.NO
Circuit
breaker
(A)
Contactor
(A)
Power
terminals Cable
Specifications
(mm
2
)
Ground
terminal cable
specifications
(mm
2
)
Terminal
screws
Specificati
ons
3-Phase
:
220V
,
50/60Hz Range
:
-15%
~
+30%
FR200-2T-0.7B
16
10
2.5
2.5
M4
FR200-2T-1.5B
25
16
4.0
4.0
M4
FR200-2T-2.2B
32
25
4.0
4.0
M4
FR200-2T-4.0B
40
32
4.0
4.0
M4
FR200-2T-5.5B
63
40
6.0
6.0
M5
FR200-2T-7.5B
63
40
6.0
6.0
M5
FR200-2T-011B
100
63
10
10
M6
FR200-2T-015B
100
63
16
10
M6
FR200-2T-018
160
100
16
16
M8
FR200-2T-018B
FR200-2T-022
200
125
25
16
M8
FR200-2T-022B
FR200-2T-030
200
125
35
25
M8
FR200-2T-030B
FR200-2T-037
250
160
50
25
M8
FR200-2T-037B
FR200-2T-045
250
160
70
35
M10
FR200-2T-055
350
350
120
60
M10
FR200-2T-075
400
400
150
75
M10
3-Phase
:
380V
,
50/60Hz Range
:
-15%
~
+30%
FR200-4T-0.7G/1.5PB
10
10
2.5
2.5
M4
FR200-4T-1.5G/2.2PB
16
10
2.5
2.5
M4
FR200-4T-2.2GB
16
10
2.5
2.5
M4
FR200-4T-4.0G/5.5PB
25
16
4.0
4.0
M4
FR200-4T-5.5G/7.5PB
32
25
4.0
4.0
M4
FR200-4T-7.5G/011PB
40
32
4.0
4.0
M4
FR200-4T-011G/015PB
63
40
6.0
6.0
M5
FR200-4T-015G/018PB
63
40
6.0
6.0
M5
FR200-4T-018G/022PB
100
63
10
10
M6
FR200-4T-022G/030PB
100
63
10
10
M6
FR200-4T-030G/037PB
100
63
16
10
M6
FR200-4T-037G/045P
160
100
16
16
M8
FR200-4T-037G/045PB
FR200-4T-045G/055P
200
125
25
16
M8
FR200-4T-045G/055PB
FR200-4T-055G/075P
200
125
35
25
M8
FR200-4T-055G/075PB
FR200-4T-075G/090P
250
160
50
25
M8
FR200-4T-075G/090PB
FR200-4T-090G/110P
250
160
70
35
M10