FR200 Series Vector control inverter
- 91 -
14.04
~
F14.06 for details. When the length is attained, digital
output terminal "length attained" shall output effective signal.
The current length value will be memorized on power loss.
35
Length clear
Used with "length count" terminal, to clear the length
calculated.
36
DC brake input
command at stop
When inverter is in the process of ramp-to-stop, and running
frequency < DC brake frequency (Set by F02.13) at stop, if the
terminal is ON, DC brake starts, until the terminal is OFF, DC
brake ends.
If the terminal is ON, and DC brake setting time is effective,
take the bigger value between time when terminal is ON and
DC brake setting time at stop.
37
Speed/torque
control switch
When motor control mode is sensor-less vector control 2 and
inverter stop, inverter will switch from speed control mode to
torque control mode if this function is valid
38
~
99
Reserved
The four multi-reference terminals have 16 state combinations, corresponding to 16 reference values,
as listed in the following table.
Table 1 State combination of the four multi-reference terminals
Multi-reference
terminal 4
Multi-reference
terminal 3
Multi-reference
terminal 2
Multi-referenc
e terminal 1
Reference
Setting
Correspondin
g
Parameter
OFF
OFF
OFF
OFF
Reference
0
F12.16
OFF
OFF
OFF
ON
Reference
1
F12.01
OFF
OFF
ON
OFF
Reference
2
F12.02
OFF
OFF
ON
ON
Reference
3
F12.03
OFF
ON
OFF
OFF
Reference
4
F12.04
OFF
ON
OFF
ON
Reference
5
F12.05
OFF
ON
ON
OFF
Reference
6
F12.06
OFF
ON
ON
ON
Reference
7
F12.07
ON
OFF
OFF
OFF
Reference
8
F12.08
ON
OFF
OFF
ON
Reference
9
F12.09
ON
OFF
ON
OFF
Reference
10
F12.10
ON
OFF
ON
ON
Reference
11
F12.11
ON
ON
OFF
OFF
Reference
12
F12.12
ON
ON
OFF
ON
Reference
13
F12.13
ON
ON
ON
OFF
Reference
14
F12.14
ON
ON
ON
ON
Reference
15
F12.15
Table 2 State combinations of two terminals for acceleration/deceleration time selection