FR200 Series Vector control inverter
- 76 -
U00.24
Accumulative power-on
time
0
~
65535min
0min
⊙
U00.25
Accumulative running time
0
~
6553.5min
0.0min
⊙
U00.26
Cumulative power-on
time
0
~
65535h
0h
⊙
U00.27
Cumulative running time
0
~
65535h
0h
⊙
U00.28
Count value
0
~
65535
0
⊙
U00.29
Length value
0
~
65535m
0m
⊙
U00.30
Linear speed
0
~
65535m/min
0m/Min
U00.31
Output torque
0.0
~
300.0%
0.0%
⊙
U00.32
PTC motor temperature
detection
-40
℃~
200
℃
0
℃
⊙
Group U01 Fault Record
U01.00
Code of the latest fault
0: No fault
0
⊙
Err01
:
Accel overcurrent
Err02
:
Decel overcurrent
Err03
:
Constant-speed overcurrent
Err04
:
Accel overvoltage
Err05
:
Decel overvoltage
Err06
:
Constant-speed overvoltage
Err07
:
Bus undervoltage
Err08
:
Short circuit
Err09
:
Power input phase loss
Err10
:
Power output phase loss
Err11
:
Motor overload
Err12
:
Inverter overload
Err13
:
External equipment fault
Err14
:
Module overheat
Err15
:
EEPROM read/write fault
Err16
:
Motor auto-tuning cancelled
Err17
:
Motor auto-tuning fault
Err18
:
Communication overtime
error
Err19
:
PID feedback loss
Err20
:
Continuous running time
reached
Err21
:
Parameter upload fault
Err22
:
Parameter download fault
Err23
:
Braking unit fault
Err24
:
Module temperature
detection disconnection
Err25: Load becoming 0
Err26
:
With-wave current limit fault
Err27
:
Inverter soft-start relay is off
Err28
:
Software version
compatibility fault
Err29
:
Instantaneous overcurrent
Err30
:
Instantaneous overvoltage
Err39
:
PTC motor temperature too
high
Err40
:
Setting operation time ends