FR200 Series Vector control inverter
- 94 -
The parameters are set as below:
Function Code
Parameter Name
Value
Function Description
F04.15
Terminal command mode
2
Three-line 1
F04.00
DI1 function selection
1
Forward RUN (FWD)
F04.01
DI2 function selection
2
Reverse RUN (REV)
F04.02
DI3 function selection
3
Three-line control
FWD
REV
GND
SB2
Three-line
control DIi
SB1
SB3
Inverter
Figure 6-10 setting of three-line mode 1
As shown in the preceding figure, if SB1 is ON, the AC drive instructs forward rotation when SB2
is pressed to be ON and instructs reverse rotation when SB3 is pressed to be ON. The AC drives
stops immediately after SB1 becomes OFF. During normal startup and running, SB1 must remain ON.
The AC drive's running state is determined by the final actions on SB1, SB2 and SB3.
3: Three-line mode 2
In this mode, DI3 is RUN enabled terminal. The RUN command is given by DI1 and the direction
is decided by DI2. The parameters are set as below:
Function Code
Parameter Name
Value
Function Description
F04.15
Terminal command
mode
3
Three-line 2
F04.00
DI1 function selection
1
Forward RUN (FWD)
F04.01
DI2 function selection
2
Reverse RUN (REV)
F04.02
DI3 function selection
3
Three-line control
FWD
REV
GND
SB2
SB1
K
Inverter
Three-line
control DIi