5. Access Procedure
Festo P.BE-CMMP-CO-SW-EN 0708NH
27
UINT8 / INT8
Read commands
Write commands
Low byte of the main index (hex)
Identifier for 8 bit
High byte of the main index
(hex)
Subindex (hex)
Command
40h IX0 IX1 SU
2Fh IX0 IX1 SU DO
Reply:
4Fh IX0 IX1 SU D0
60h IX0 IX1 SU
UINT16 / INT16
Identifier for 8 bit
Identifier for 16 bit
Command
40h IX0 IX1 SU
2Bh IX0 IX1 SU DO D1
Reply:
4Bh IX0 IX1 SU D0 D1
60h IX0 IX1 SU
UINT32 / INT32
Identifier for 16 bit
Identifier for 32 bit
Command
40h IX0 IX1 SU
23h IX0 IX1 SU DO D1 D2 D3
Reply:
43h IX0 IX1 SU D0 D1 D2 D3
60h IX0 IX1 SU
Identifier for 32 bit
EXAMPLE
UINT8 / INT8
Reading obj. 6061_00
h
Return data: 01
h
Writing obj. 1401_02
h
Data: EF
h
Command
40
h
61
h
60
h
00
h
2F
h
01
h
14
h
02
h
EF
h
Reply:
4F
h
61
h
60
h
00
h
01
h
60
h
01
h
14
h
02
h
UINT16 / INT16
Reading obj. 6041_00
h
Return data: 1234
h
Writing obj. 6040_00
h
Data: 03E8
h
Command
40
h
41
h
60
h
00
h
2B
h
40
h
60
h
00
h
E8
h
03
h
Reply:
4B
h
41
h
60
h
00
h
34
h
12
h
60
h
40
h
60
h
00
h
UINT32 / INT32
Reading obj. 6093_01
h
Return data: 12345678
h
Writing obj. 6093_01
h
Data: 12345678
h
Command
40
h
93
h
60
h
01
h
23
h
93
h
60
h
01
h
78
h
56
h
34
h
12
h
Reply:
43
h
93
h
60
h
01
h
78
h
56
h
34
h
12
h
60
h
93
h
60
h
01
h
Caution
The acknowledgement from the motor controller must always be
waited for!
Only when the motor controller has acknowledged the request may
additional requests be sent.