5. Access Procedure
34
Festo P.BE-CMMP-CO-SW-EN 0708NH
Note that parameter setting of the PDOs may generally only be
changed when the network status (NMT) is not
operational
.
See also chapter 5.3.3.
5.3.2
Objects for PDO Parameter Setting
The motor controllers of the CMMP series contain a total of 4 transmit and 4 receive PDOs.
The individual objects for setting parameters for these PDOs are the same for all TPDOs
and all RPDOs in each case. For that reason, only the parameter description of the first
TPDO is explicitly listed. The meaning can also be used for the other PDOs, which are
listed in table form in the following:
Index
1800
h
Name
transmit_pdo_parameter_tpdo1
Object code
RECORD
No. of Elements
3
Sub-index
01
h
Description
cob_id_used_by_pdo_tpdo1
Data Type
UINT32
Access
rw
PDO Mapping
no
Units
--
Value Range
181
h
… 1FF
h
, bit 30 and 31 may be set
Default Value
C0000181
h
Sub-index
02
h
Description
transmission_type_tpdo1
Data Type
UINT8
Access
rw
PDO Mapping
no
Units
--
Value Range
0 … 8C
h
, FE
h
, FF
h
Default Value
FF
h