6. Setting Parameters
78
Festo P.BE-CMMP-CO-SW-EN 0708NH
Object 6073
h
: max_current
Servo motors may normally be overloaded for a certain time period. The highest
permissible motor current is set with this object. It refers to the motor rated current
(object
6075
h
: motor_rated_current
) and is set in thousandths. The value range is limited
upward by the maximum controller current (object
6510
h
_ 41
h
: peak_current
). Many
motors may be overloaded by a factor of 2 for a short time. In this case, write the value
2000 in this object.
The object
6073
h
(
max_current
) may only be written when the
object
6075
h
(
motor_rated_current
) was previously validly written.
Index
6073
h
Name
max_current
Object code
VAR
Data Type
UINT16
Access
rw
PDO Mapping
yes
Units
per thousands of rated current
Value Range
--
Default Value
2023
Object 604D
h
: pole_number
The number of poles of the motor can be obtained from the motor datasheet or the
parameterisation software. The number of poles is always an even number. Often, the
number of pole pairs is given instead of the number of poles. The number of poles then
equals twice the number of pole pairs.
This object is not changed through
restore_default_parameters
.
Index
604D
h
Name
pole_number
Object code
VAR
Data Type
UINT8
Access
rw
PDO Mapping
yes
Units
--
Value Range
2 … 254
Default Value
4 (after INIT!)