8. Operating modes
166
Festo P.BE-CMMP-CO-SW-EN 0708NH
Method -1: Negative stop with zero pulse evaluation
With this method, the drive first moves in a negative direction until it reaches the stop.
The I
2
t integral of the motor rises hereby to a maximum 90 %. The stop must be
mechanically dimensioned so that it does not suffer damage in the parameterised
maximum current. The zero position refers to the first zero pulse of the angle transmitter
in the positive direction from the stop.
Fig. 8.11: Reference travel to the negative stop with evaluation of the zero pulse
Method -2: Positive stop with zero pulse evaluation
With this method, the drive first moves in a positive direction until it reaches the stop.
The I
2
t integral of the motor rises hereby to a maximum 90 %. The stop must be
mechanically dimensioned so that it does not suffer damage in the parameterised
maximum current. The zero position refers to the first zero pulse of the angle transmitter
in the negative direction from the stop.
Fig. 8.12: Reference travel to the positive stop with evaluation of the zero pulse
Method -17: Reference travel to the negative stop
With this method, the drive first moves in a negative direction until it reaches the stop.
The I
2
t integral of the motor rises hereby to a maximum 90 %. The stop must be
mechanically dimensioned so that it does not suffer damage in the parameterised
maximum current. The zero position refers directly to the stop.
Fig. 8.13: Reference travel to the negative stop