6. Setting Parameters
112
Festo P.BE-CMMP-CO-SW-EN 0708NH
Sub-index
03
h
Description
analog_input_voltage_ch_2
Access
ro
PDO Mapping
no
Units
mV
Value Range
--
Default Value
--
Object 2401
h
: analog_input_offset (offset analogue inputs)
With the object group
analog_input_offset
, the offset voltage in millivolts can be set or
read for the respective inputs. With the offset, any direct voltage present can be
compensated for. A positive offset thereby compensates for a positive input voltage.
Index
2401
h
Name
analog_input_offset
Object code
ARRAY
No. of Elements 3
Data Type
INT32
Sub-index
01
h
Description
analog_input_offset_ch_0
Access
rw
PDO Mapping
no
Units
mV
Value Range
-10000 … 10000
Default Value
0
Sub-index
02
h
Description
analog_input_offset_ch_1
Access
rw
PDO Mapping
no
Units
mV
Value Range
-10000 … 10000
Default Value
0
Summary of Contents for CMMP Series