6. Setting Parameters
74
Festo P.BE-CMMP-CO-SW-EN 0708NH
Object 6510
h
_ 36
h
: min_dc_link_circuit_voltage
The motor controller has an undervoltage monitor. It can be activated via the object
6510
h
_ 37
h
(
enable_dc_link_undervoltage_error
). The object
6510
h
_ 36
h
(
min_dc_link_circuit_voltage
) specifies the lower intermediate circuit voltage the motor
controller should work up to. Below this voltage, the error E 02-0 is triggered if it was
activated by the following object.
Sub-index
36
h
Description
min_dc_link_circuit_voltage
Data Type
UINT32
Access
rw
PDO Mapping
no
Units
mV
Value Range
0 … 1 000 000
Default Value
0
Object 6510
h
_ 37
h
: enable_dc_link_undervoltage_error
The undervoltage monitor can be activated with the object
enable_dc_link_
undervoltage_error
. In the object
6510
h
_ 36
h
(
min_dc_link_circuit_voltage
), specify the
lower intermediate circuit voltage the motor controller should work up to.
Sub-index
37
h
Description
enable_dc_link_undervoltage_error
Data Type
UINT16
Access
rw
PDO Mapping
no
Units
--
Value Range
0, 1
Default Value
0
Value
Meaning
0
Undervoltage error OFF (reaction WARNING)
1
Undervoltage error ON (Reaction CONTROLLER ENABLE OFF)
The error 02-0 is activated through a change of the error reaction. Reactions that lead to
shutting down of the drive are returned as
ON
, all others as
OFF
. When writing with 0, the
error reaction WARNING is set, when writing with 1 the error reaction CONTROLLER
ENABLE OFF.
See also chapter 6.18, Error management.