Field Setting
Test Operation
204
BRC7C Type
BRC7E Type
BRC4C Type
Group No. setting by wireless remote controller for centralized control
1. When in the normal mode, push “
” button for 4 seconds or more, and operation then
enters the “field set mode.”
2. Set mode No. “00” with “
” button.
3. Set the group No. for each group with “
” “
” button (advance/backward).
4. Enter the selected group numbers by pushing “
” button.
5. Push “
” button and return to the normal mode.
Group No. Setting
Example
Caution
When turning the power supply on, the unit may often not accept any operation while "88" is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.
MODE NO.
FIELD SET MODE
3
4
GROUP NO.
2
1, 5
(V0916)
Indoor/Outdoor Outdoor/Outdoor
F1 F2
F1 F2
Indoor/Outdoor Outdoor/Outdoor
F1 F2
F1 F2
Centralized Remote
Controller
F1 F2
F1 F2 P1 P2
RC
1-00
F1 F2 P1 P2
RC
1-01
RC Sub
Main
F1 F2 P1 P2
RC
1-02
F1 F2 P1 P2
Group Control by Remote
Controller (automatic unit address)
F1 F2 P1 P2
No Remote Controller
1-03
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
RC
1-04
(V0917)