SiBE37-701_B
Troubleshooting by Indication on the Remote Controller
Troubleshooting
356
3.54
“
U8
”
Indoor Unit: Malfunction of Transmission between
Main and Sub Remote Controllers
Remote
Controller
Display
U8
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using micro-computer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Malfunction of transmission between main and sub remote controller
Connection between sub remote controllers
Defect of remote controller PCB
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Set SS1 to "MAIN"; the
power supply off once and
then back on.
YES
Using 2-remote
controllers control.
NO
NO
YES
YES
NO
SS1 of both remote
controllers is set to
"SUB."
SS1 of remote
controller PCBs is
set to "MAIN."
Turn the power off and
then back on. If a
malfunction occurs,
replace the remote
controller PCB.
Set one remote controller
to "MAIN"; the power
supply off once and then
back on.
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...