Specifications
SiBE37-701_B
43
Specifications
Concealed Ceiling Unit
1-1 TECHNICAL SPECIFICATIONS
FXSQ63P7VEB
FXSQ80P7VEB
FXSQ100P7VEB
FXSQ125P7VEB
Piping
connections
Liquid
(OD)
Type
Flare connection
Diameter
mm
9.52
Gas
Type
Flare connection
Diameter
mm
15.9
Drain
Diameter
mm
VP25 (O.D. 32 / I.D. 25)
Heat Insulation
Both liquid and gas pipes
Decoration
Panel
Model
BYBS71DJW1
BYBS71DJW1
BYBS125DJW1
BYBS125DJW1
Colour
White (10Y9/0,5)
Dimensions Height
mm
55
Width
mm
1,100
1,100
1,500
1,500
Depth
mm
500
Weight
kg
4.5
4.5
6.5
6.5
Drain-up Height
mm
625
Air Filter
Resin net with mold resistance
Refrigerant control
Electronic expansion valve
Safety devices
PCB fuse
PCB fuse (fan driver)
Drain pump fuse
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 7.5m, level difference : 0m.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The sound pressure values are mentioned for a unit installed with rear suction
1-2 ELECTRICAL SPECIFICATIONS
FXSQ20P7VEB
FXSQ25P7VEB
FXSQ32P7VEB
FXSQ40P7VEB
FXSQ50P7VEB
Power
Supply
Name
VE
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps
(MCA)
A
0.4
0.4
0.4
1.2
1.2
Maximum fuse amps
(MFA)
A
16
Voltage
range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-1 ELECTRICAL SPECIFICATIONS
FXSQ63P7VEB
FXSQ80P7VEB
FXSQ100P7VEB
FXSQ125P7VEB
Power
Supply
Name
VE
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps
(MCA)
A
1.1
1.3
1.6
2.1
Maximum fuse amps
(MFA)
A
16
Voltage
range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...