SiBE37-701_B
Field Setting
Test Operation
198
(6) Optional Output Switching
Using this setting, "operation output signal" and "abnormal output signal" can be provided.
Output signal is output between terminals K1 and K2 of "customized wiring adaptor," an optional
accessory.
(7) External ON/OFF input
This input is used for "ON / OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T2 terminal of the operation terminal block (X1A) in the electric
component box.
Setting Table
(8) Thermostat Switching
Differential value during thermostat ON/OFF control can be changed. (For details, refer to "6.2.2
Thermostat Control while in Normal Operation" on P.145.)
(9) Airflow Setting When Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
∗
When thermostat OFF airflow volume up mode is used, careful consideration is required
before deciding installation location. During heating operation, this setting takes precedence
over "(7) Fan Stop When Thermostat is OFF."
(10) Setting of operation mode to "AUTO"
This setting makes it possible to change differential values for mode selection while in automatic
operation mode.
The automatic operation mode setting is made by the use of the "Operation Mode Selector"
button.
Mode No.
First Code No.
Second Code No.
Remarks
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is
provided.
03
Output linked with "Start/Stop" of remote
controller is provided.
04
In case of "Malfunction Display" appears
on the remote controller, output is
provided.
F2 T1 T2
Forced stop
Input A
Mode No.
First Code
No.
Second
Code No.
Operation by input of the signal A
12 (22)
1
01
ON: Forced stop (prohibition of using the remote
controller)
OFF: Permission of using the remote controller
02
OFF
→
ON: Permission of operation
ON
→
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit
indicates "A0". The other indoor units indicate "U9".
Mode No.
First Code No.
Second Code No.
Differential value
12(22)
2
01
1ºC
02
0.5ºC
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
3
01
LL airflow
02
Preset airflow
Mode No.
First Code No.
Second Code No.
01
02
03
04
05
06
07
08
12 (22)
4
0°C
1°C
2°C
3°C
4°C
5°C
6°C
7°C
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...