SiBE37-701_B
Test Operation
Test Operation
164
[Stop Valve Operation Procedure]
When operating the stop valve, follow the procedure instructed below.
Note:
Do not open the stop valve until “1.2.1 Check work prior to turn power supply on” in page
157 are completed. If the stop valve is left open without turning on the power, it may cause
refrigerant to buildup in the compressor, leading insulation degradation.
Be sure to use the correct tools.
The stop valve is not a back-seat type. If forced it to open, it might break the valve body.
When using a service port, use the charge hose.
After tightening the cap, make sure no refrigerant gas is leaking.
[Tightening torque]
The sizes of the stop valves on each model and the tightening torque for each size are listed in
the table below.
<Size of Stop Valve>
REYQ8~16PY1B
REYQ18~48P7Y1B
8HP type
10HP type
12HP type
14HP type
16HP type
Liquid pipe stop valve
φ
9.5
φ
12.7
The 12HP type corresponds to the 12.7-
diameter onsite piping using the accessory
pipe.
Suction gas stop valve
φ
25.4
The 8HP type corresponds to the 19.1-diameter onsite piping using the
accessory pipe.
The 10HP type corresponds to the 22.2-diameter onsite piping using the
accessory pipe.
The 12-16 HP type corresponds to the 28.6-diameter onsite piping using
the accessory pipe.
HP/LP gas stop valve
φ
19.1
The 8HP type corresponds to the 15.9-diameter onsite piping using the
accessory pipe.
The 14·16 HP type corresponds to the 22.2-diameter onsite piping using
the accessory pipe.
8HP type
10HP type
12HP type
14HP type
16HP type
Liquid pipe stop valve
φ
9.5
φ
12.7
The 12HP type corresponds to the 12.7-
diameter onsite piping using the accessory
pipe.
Suction gas stop valve
φ
25.4
The 8 · 10HP type corresponds to the 22.2-diameter onsite piping using
the accessory pipe.
The 12-16 HP type corresponds to the 28.6-diameter onsite piping using
the accessory pipe.
HP/LP gas stop valve
φ
19.1
The 14 · 16 HP type corresponds to the 22.2-diameter onsite piping
using the accessory pipe.
Equalizer pipe stop valve
φ
19.1
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...