Special Control
SiBE37-701_B
127
Function
Evaporating outdoor unit actuator
Symbol
Elect. symbol
Defrost operation
Operation after defrost
REYQ REMQ
Compressor 1
—
M1C
M1C
REYQ8•10•12P: 232Hz+ON
REYQ14•16P: 232Hz+232Hz
REMQ8P: 210Hz
REMQ10•12P: 210Hz+ON
REMQ14•16P: 210Hz+ON+ON
Upper limit 124Hz (STD Holds)
REYP400•480A: 232Hz+232Hz
REMP224A: 210Hz
REMP280•335A: 210Hz+ON
REMP400•450A:
210Hz+ON+ON
Compressor 2
M2C
M2C
Compressor 3
M3C
M3C
Outdoor unit fan 1
—
M1F
M1F
Fan control
Fan control
Outdoor unit fan 2
M2F
M2F
Four way valve (Heat exchanger
switch)
20SA
Y2S
Y9S
Y3S
ON
ON
Four way valve (Dual pressure gas
pipe switch)
20SB
Y8S
Y2S
Holds
Holds
Electronic expansion valve (Main)
EVM
Y1E
Y3E
Y1E
PI control
PI control
Electronic expansion valve
(Subcooling)
EVT
Y2E
Y5E
Y3E
SH control
0pls
Electronic expansion valve
(Refrigerant charge)
EVJ
Y4E
Y2E
80pls
80pls
Solenoid valve (Main bypass)
SVE
Y5S
Y10S
Y6S
OFF
OFF
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
OFF
Solenoid valve (Refrigerant
regulator liquid pipe)
SVL
Y3S
Y4S
0pls
0pls
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG
Y1S
Y1S
0pls
0pls
Solenoid valve (Refrigerant
regulator discharge pipe)
SVO
Y7S
Y7S
0pls
0pls
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT
Y6S
Y8S
0pls
0pls
Cooling indoor unit actuator
Defrost operation
Fan
Thermo. ON unit
Remote controller setting
Unit not in operation
OFF
Thermo. OFF unit
Remote controller setting
Electronic expansion valve
Thermo. ON unit
Normal opening degree
Unit not in operation
0pls
Thermo. OFF unit
0pls
Heating indoor unit actuator
Defrost operation
REYQ
REMQ
Fan
Thermo. ON unit
LL
LL
Unit not in operation
OFF
OFF
Thermo. OFF unit
LL
LL
Electronic expansion valve
Thermo. ON unit
160pls
224pls
Unit not in operation
0pls
0pls
Thermo. OFF unit
160pls
224pls
Cooling BS unit actuator
Elect. symbol
Defrost operation
Electronic expansion valve (EVH)
Y4E
0pls
Electronic expansion valve (EVL)
Y5E
760pls
Electronic expansion valve (EVHS)
Y2E
0pls
Electronic expansion valve (EVLS)
Y3E
480pls
Electronic expansion valve (EVSC)
Y1E
0pls
Heating BS unit actuator
Elect. symbol
Defrost operation
Electronic expansion valve (EVH)
Y4E
760pls
Electronic expansion valve (EVL)
Y5E
0pls
Electronic expansion valve (EVHS)
Y2E
60pls
Electronic expansion valve (EVLS)
Y3E
0pls (REYQ8~16P) 60pls (REMQ8~16P)
Electronic expansion valve (EVSC)
Y1E
0pls (PI control for cool/heat concurrent operation)
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...