SiBE37-701_B
Field Setting
Test Operation
220
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
*1: Number of connected indoor units
Used to make setting of the number of indoor units connected to an outdoor
unit.
*2: Number of connected BS units
Used to make setting of the number of BS units connected to an outdoor
unit.
*3: Number of outdoor units
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
*4: Number of BS units
Used to make setting of the number of BS units connected to DIII-NET that is
one of the communication lines.
*5: Number of terminal units
Used to make setting of the number of indoor units connected to DIII-NET
that is one of the communication lines.
(Only available for VRV indoor units)
No.
Setting item
LED display
Data display
H1P
H2P
H3P
H4P
H5P
H6P
H7P
0
Various settings
l h h h h h h
Lower 4 digits
1
C/H unified address
l h h h h h k
Lower 6 digits
2
Low noise/demand address
l h h h h k h
3
Not used
l h h h h k k
4
AIRNET address
l h h h k h h
5
Number of connected indoor units
*1
l h h h k h k
6
Number of connected BS units *2
l h h h k k h
7
Number of connected zone units
(Fixed to "0")
l h h h k k k
8
Number of outdoor units *3
l h h k h h h
9
Number of BS units *4
l h h k h h k
Lower 4 digits:
upper
10
Number of BS units *4
l h h k h k h
Lower 4 digits:
lower
11
Number of zone units
l h h k h k k
Lower 6 digits
12
Number of terminal units *5
l h h k k h h
Lower 4 digits:
upper
13
Number of terminal units *5
l h h k k h k
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
l h h k k k h
Malfunction
code table
Refer page
255.
15
Contents of malfunction
(1 cycle before)
l h h k k k k
16
Contents of malfunction
(2 cycle before)
l h k h h h h
20
Contents of retry (the latest)
l h k h k h h
21
Contents of retry (1 cycle before)
l h k h k h k
22
Contents of retry (2 cycle before)
l h k h k k h
25
Number of multi connection
outdoor units
l h k k h h k
Lower 6 digits
c. Monitor mode
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
<Selection of setting item>
Push the SET (BS2) button and set
the LED display to a setting item.
<Confirmation on setting contents>
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
* Push the MODE (BS1) button and
returns to “Setting mode 1”.
(V2765)
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...