![Daikin REYQ8-48PY1B Service Manual Download Page 360](http://html.mh-extra.com/html/daikin/reyq8-48py1b/reyq8-48py1b_service-manual_502202360.webp)
Troubleshooting by Indication on the Remote Controller
SiBE37-701_B
349
Troubleshooting
3.52
“
U5
”
Indoor Unit: Malfunction of Transmission between
Remote Controller and Indoor Unit
Remote
Controller
Display
U5
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using micro-computer is signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Malfunction of indoor unit remote controller transmission
Connection of two main remote controllers (when using 2 remote controllers)
Defect of indoor unit PCB
Defect of remote controller PCB
Malfunction of transmission caused by noise
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Set one remote controller to
"SUB"; turn the power supply
off once and then back on.
Using 2-remote
controllers control.
YES
SS1 of both remote
controllers is set to
"MAIN."
All indoor PCB
micro-computer
monitors blink.
Replace the remote controller
Normal
Replace the indoor unit PCB.
Normal
Operation returns to
normal when the power is
turned off momentarily.
YES
NO
NO
NO
NO
YES
YES
NO
NO
YES
YES
Replace the indoor unit PCB.
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
Normal
Normal
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...