Refrigerant Circuit
SiBE37-701_B
69
Refrigerant Circuit
1.6
BS Unit Functional Parts
BSV4Q100PV1, 6Q100PV1
Note :
Factory setting of all EV opening : 60pls
No.
Name
Symbol
Function
1
Electronic expansion valve (EVH)
Y4E
Opens while in heating operation or all indoor units are in cooling
operation. (Max : 760pls)
2
Electronic expansion valve (EVL)
Y5E
Opens while in cooling operation. (Max : 760pls)
3
Electronic expansion valve (EVHS)
Y2E
Opens while in heating operation or all indoor units are in cooling
operation. (Max : 480pls)
4
Electronic expansion valve (EVLS)
Y3E
Opens while in cooling operation. (Max : 480pls)
5
Electronic expansion valve (EVSC)
Y1E
In simultaneous cooling and heating operation, it is used to subcooling
liquid refrigerants when an indoor unit downstream of this BS unit is in
heating operation. (Max : 480pls)
6
Capillary tube
—
Used to bypass high pressure gas to low pressure side to protect
“Refrigerant accumulation” in high and low pressure gas pipes.
Liquid
Liquid
Indoor
side
Outdoor
side
Gas
Dual Pressure
Suction
(5)
(6)
(3)
(1)
(4)
(2)