Field Setting
SiBE37-701_B
201
Test Operation
(18) External Static Pressure Settings (for FXMQ-P model)
The “SECOND CODE NO.” is set to 07 (an external static pressure of 100 Pa) at factory setting.
*1 The FXMQ50 · 63 · 80 · 100 · 125 · 140PVE cannot be set to 30 Pa.
*2 The FXMQ20 · 25 · 32 · 40PVE cannot be set to 180 or 200 Pa.
(19) Humidification When Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction air temperature is 20ºC or
above and turns OFF the humidifier if suction air temperature is 18ºC or below when the heating
thermostat is OFF.
(20) Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries
out residual operation for one minute after the thermostat is stopped. (For the purpose of
preventing dust on the air filter from falling off.)
(21) Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the
unit, this setting is unnecessary.
MODE NO.
FIRST CODE NO.
SECOND CODE NO.
External Static Pressure
13 (23)
06
01
30Pa (*1)
02
50Pa
03
60Pa
04
70Pa
05
80Pa
06
90Pa
07
100Pa
08
110Pa
09
120Pa
10
130Pa
11
140Pa
12
150Pa
13
160Pa
14
180Pa (*2)
15
200Pa (*2)
Mode No.
First Code No.
Second Code No.
Setting
15 (25)
1
01
—
02
Setting of humidifier
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
2
01
Without direct duct
connection
02
With direct duct
connection equipped
with fan
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
3
01
Individual operation of
humidifier
02
Interlocked operation
between humidifier and
drain pump
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...