SiBE37-701_B
Test Operation
Test Operation
158
•
Calculate a necessary additional refrigerant charging amount according to the procedure for
calculation shown below.
*
Procedure for calculating additional refrigerant charging amount (Unit: 0.1 kg)
Correction amount with indoor unit
Correction amount with a total capacity of indoor units
•
If there is a refrigerant shortage, charge a liquid refrigerant through the stop valve service
port with the stop valves of liquid and those of gas closes after the completion of vacuum
drying.
•
If the refrigerant charging is still insufficient, "turn ON the power supply" following the
information on the page 162 ~.
Check on amount of refrigerant
charge
{
Is a proper quantity of refrigerant charged?
The following method is available for additional charging of
refrigerant.
(1) Calculate additional refrigerant quantity.
System name
Correction
amount
Ratio of total capacity of the
connected indoor units to
the rated capacity of the
outdoor unit (A)
Correction amount
Model REYQ8-16PY1B
3.6 kg
Model REYQ18-20P7Y1B
1.0kg
Model
REYQ18 -
32P7Y1B
Model
REYQ34 -
48P7Y1B
Model REYQ22-24P7Y1B
1.5kg
+
Model REYQ26P7Y1B
2.0kg
+
Model REYQ28-30P7Y1B
2.5kg
100%<A
≤
120
%
0.5kg
Model REYQ32-40P7Y1B
3.0kg
120%<A
≤
130
%
0.5kg
1.0kg
Model REYQ42P7Y1B
3.5kg
Model REYQ44-46P7Y1B
4.0kg
Model REYQ48P7Y1B
4.5kg
R
Total length of
φ
22.2-mm
liquid pipe)
Total length of
φ
19.1-mm
liquid pipe)
Total length of
φ
15.9-mm
liquid pipe)
Total length of
φ
12.7-mm
liquid pipe)
Total length of
φ
9.5-mm
liquid pipe)
Total length of
φ
6.4-mm
liquid pipe)
× 0.37
× 0.26
× 0.18
× 0.12
× 0.059
× 0.022
× 1.02
Check the stop valves for
conditions.
{
Has the additional refrigerant charging amount been
recorded on the "Precautions for servicing" label?
{
Check to be sure the stop valves are under the following
conditions.
Liquid-pipe
stop valve
Equalizing pipe
stop valve
Dual pressure gas
pipe stop valve
Suction pipe
stop valve
Open
Open
Open
Open
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...