Special Control
SiBE37-701_B
123
Function
Cooling indoor unit actuator
Oil return operation
Fan
Thermo. ON unit
Remote controller setting
Unit not in operation
OFF
Thermo. OFF unit
Remote controller setting
Electronic expansion valve
Thermo. ON unit
Normal opening degree
Unit not in operation
192pls
Thermo. OFF unit
Normal opening degree for forced thermostat ON
Cooling BS unit actuator
Elect. symbol
Oil return operation
Electronic expansion valve (EVH)
Y4E
600pls
Electronic expansion valve (EVL)
Y5E
760pls
Electronic expansion valve (EVHS)
Y2E
480pls
Electronic expansion valve (EVLS)
Y3E
480pls
Electronic expansion valve (EVSC)
Y1E
0pls