Refrigerant Flow for Each Operation Mode
Refrigerant Circuit
102
2. When switching operation from heating to cooling
First, the electronic expansion valve and the solenoid valve for EVHS, EVH, EVL and EVLS
of the indoor unit will be closed.
Next, open the EVLS, and it makes to balance the system pressure.
Finally, EVL and EVLS are opened and the electronic expansion valve of the indoor unit is
opened to start the operation as a cooling circuit.
In heating
operation
In equalization
To cooling
operation
Indoor Unit
BS Unit
Heating
Unit
EVSC
Liquid
Pipe
EVHS
EVH
EVLS
EVL
Dual
Pressure
Gas Pipe
Suction
Pipe
Indoor Unit
BS Unit
EVSC
Liquid
Pipe
EVHS
(Close)
EVH
(Close)
EVLS
(Close)
EVL (Open)
Dual
Pressure
Gas Pipe
Suction
Pipe
(Close)
In
equalization
Indoor Unit
BS Unit
Cooling
Unit
EVSC
Liquid
Pipe
EVHS
EVH
EVLS
EVL
Dual
Pressure
Gas Pipe
Suction
Pipe