Precautions for New Refrigerant (R-410A)
SiBE37-701_B
459
Precautions for New Refrigerant (R-410A)
1.3
Service Tools
R-410A is used under higher working pressure, compared to previous refrigerants (R-22, R-407C).
Furthermore, the refrigerating machine oil has been changed from Suniso oil to Ether oil, and if
oil mixing is occurred, sludge results in the refrigerants and causes other problems. Therefore,
gauge manifolds and charge hoses that are used with a previous refrigerant (R-22, R-407C) can
not be used for products that use new refrigerants.
Be sure to use dedicated tools and devices.
Tool compatibility
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
Copper tube material and thickness
* O: Soft (Annealed)
H: Hard (Drawn)
Tool
Compatibility
Reasons for change
HFC
HCFC
R-410A
R-407C
R-22
Gauge manifold
Charge hose
✕
•
Do not use the same tools for R-22
and R-410A.
•
Thread specification differs for
R-410A and R-407C.
Charging cylinder
✕
{
•
Weighting instrument used for HFCs.
Gas detector
{
✕
•
The same tool can be used for HFCs.
Vacuum pump
(pump with reverse flow
preventive function)
{
•
To use existing pump for HFCs,
vacuum pump adaptor must be
installed.
Weighting instrument
{
Charge mouthpiece
✕
•
Seal material is different between
R
-
22 and HFCs.
•
Thread specification is different
between R-410A and others.
Flaring tool (Clutch type)
{
•
For R-410A, flare gauge is necessary.
Torque wrench
{
•
Torque-up for 1/2 and 5/8
Pipe cutter
{
Pipe expander
{
Pipe bender
{
Pipe assembling oil
✕
•
Due to refrigerating machine oil
change. (No Suniso oil can be used.)
Refrigerant recovery
device
Check your recovery device.
Refrigerant piping
See the chart below.
•
Only
φ
19.1 is changed to 1/2H material
while the previous material is "O".
Pipe size
R-407C
R-410A
Material
Thickness
t (mm)
Material
Thickness
t (mm)
φ
6.4
{
0.8
{
0.8
φ
9.5
{
0.8
{
0.8
φ
12.7
{
0.8
{
0.8
φ
15.9
{
1.0
{
1.0
φ
19.1
{
1.0
1/2H
1.0
φ
22.2
1/2H
1.0
1/2H
1.0
φ
25.4
1/2H
1.0
1/2H
1.0
φ
28.6
1/2H
1.0
1/2H
1.0
φ
31.8
1/2H
1.2
1/2H
1.1
φ
38.1
1/2H
1.4
1/2H
1.4
φ
44.5
1/2H
1.6
1/2H
1.6
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...