SiBE37-701_B
Field Setting
Test Operation
232
k
Disabling the compressor 2 (on the left side) from operating:
Set No. 39 of setting mode 2 to "Disable-compressor-2 operation".
<REYQ18 to 48PY1>
Make disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1. (If this setting is made on an outdoor unit other
than the outdoor unit 2, the setting will become invalid.)
* It is possible to tell the outdoor units 1, 2, and 3 according the LED displays shown below.
k
Disabling the outdoor unit 1 to operate:
Set No. 38 of setting mode 2 to "Disable outdoor unit 1 operation".
k
Disabling the outdoor unit 2 from operating:
Set No. 39 of setting mode 2 to "Disable-outdoor-unit-2 operation".
k
Disabling the outdoor unit 3 from operating:
Set No. 40 of setting mode 2 to "Disable-outdoor-unit-1 operation".
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step)
H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
k h h h h h h
(2) Press the OPERATE button (BS2) 39
times.
k k h h k k k
(3) Press the CHECK button (BS3) once.
k h h h h h l
(Factory setting)
(4) Press the OPERATE button (BS2) once.
k h h h h l h
(5) Press the CHECK button (BS3) twice.
k h h h h h h
(6) Press the PAGE button (BS1) once.
h h k h h h h
LED display (
k
: ON,
h
: OFF,
l
: Blink)
H1P-----------H7P H8P
Outdoor unit 1:
h h k h h h h
k
Outdoor unit 2:
h h h h h h h
l
Outdoor unit 3:
h h h h h h h
h
(Factory setting)
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step)
H1P-----------H7P
(1) Press and hold the PAGE button (BS1)
for 5 sec. or more.
k h h h h h h
(2) Press the OPERATE button (BS2) 38
times.
k k h h k k h
(3) Press the CHECK button (BS3) once.
k h h h h h l
(Factory setting)
(4) Press the OPERATE button (BS2) once.
k h h h h l h
(5) Press the CHECK button (BS3) twice.
k h h h h h h
(6) Press the PAGE button (BS1) once.
h h k h h h h
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step)
H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
k h h h h h h
(2) Press the OPERATE button (BS2) 39
times.
k k h h k k k
(3) Press the CHECK button (BS3) once.
k h h h h h l
(Factory setting)
(4) Press the OPERATE button (BS2) once.
k h h h h l h
(5) Press the CHECK button (BS3) twice.
k h h h h h h
(6) Press the PAGE button (BS1) once.
h h k h h h h
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step)
H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
k h h h h h h
(2) Press the OPERATE button (BS2) 40
times.
k k h k h h h
(3) Press the CHECK button (BS3) once.
k h h h h h l
(Factory setting)
(4) Press the OPERATE button (BS2) once.
k h h h h l h
(5) Press the CHECK button (BS3) twice.
k h h h h h h
(6) Press the PAGE button (BS1) once.
h h k h h h h
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...