Model Selection
SiBE37-701_B
7
General Information
Connectable Indoor Unit
Note: FXDQ has following 2 Series, as shown below.
FXDQ-PB, NBVE: with Drain Pump
Indoor unit capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
The total capacity of connected indoor units must be within a range of 50 to 130% of the
rated capacity of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
Type
Model Name
Power
Supply
Roundflow Ceiling
Mounted Cassette
FXFQ
20P8
25P8
32P8
40P8
50P8
63P8
80P8
100P8 125P8
—
—
—
VEB
600×600 4-Way Blow
Ceiling Mounted
Cassette
FXZQ
20M9
25M9
32M9
40M9
50M9
—
—
—
—
—
—
—
V1B
2-Way Blow Ceiling
Mounted Cassette
FXCQ
20M8
25M8
32M8
40M8
50M8
63M8
80M8
—
125M8
—
—
—
V3B
Ceiling Mounted
Corner Cassette
FXKQ
—
25MA
32MA
40MA
—
63MA
—
—
—
—
—
—
VE
Slim Concealed Ceiling
Unit
FXDQ-
PBVE
20PB
25PB
32PB
—
—
—
—
—
—
—
—
—
FXDQ-
NBVE
—
—
—
40NB
50NB
63NB
—
—
—
—
—
—
Concealed Ceiling Unit
(Small)
FXDQ
20M9
25M9
—
—
—
—
—
—
—
—
—
—
V3B
Concealed Ceiling Unit
FXSQ
20P7
25P7
32P7
40P7
50P7
63P7
80P7
100P7 125P7
—
—
—
VEB
Concealed Ceiling Unit
FXMQ
20P
25P
32P
40P
50P
63P
80P
100P
125P
140P
—
—
VE
Concealed Ceiling Unit
(Large)
FXMQ
—
—
—
—
—
—
—
—
—
—
200MA 250MA
Ceiling Suspended Unit
FXHQ
—
—
32MA
—
—
63MA
—
100MA
—
—
—
—
Wall Mounted Unit
FXAQ
20P
25P
32P
40P
50P
63P
—
—
—
—
—
—
V1
Floor Standing Unit
FXLQ
20MA
25MA
32MA
40MA
50MA
63MA
—
—
—
—
—
—
VE
Concealed Floor
Standing Unit
FXNQ
20MA
25MA
32MA
40MA
50MA
63MA
—
—
—
—
—
—
New refrigerant model code
P20
type
P25
type
P32
type
P40
type
P50
type
P63
type
P80
type
P100
type
P125
type
P140
type
P200
type
P250
type
Selecting model capacity
2.2
kW
2.8
kW
3.5
kW
4.5
kW
5.6
kW
7.0
kW
9.0
kW
11.2
kW
14.0
kW
16.0
kW
22.4
kW
28.0
kW
Equivalent output
0.8HP
1HP
1.25HP 1.6HP 2.0HP 2.5HP 3.2HP
4HP
5HP
6HP
8HP
10HP
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...