Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting
386
[CHECK 6] Check for causes of drop in low pressure
Referring to the Fault Tree Analysis (FTA) shown below, probe the faulty points.
Faulty low
pressure
control
←
Are the electrical characteristics normal?
Abnormally low
low-pressure (Low
evaporating
temperature)
Faulty electronic
expansion valve
control
[In both cooling
and heating]
(See *2.)
[In cooling]
If the indoor unit
electronic
expansion valve is
excessively
throttled: (See *3.)
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled:
(See *4.)
[In cooling]
Low suction
air
temperature
of the
evaporator
[In heating]
Less
circulation
quantity of
refrigerant
Degradation
in condensing
capacity
[In cooling]
(See *1.)
Faulty
compressor
capacity
control
Faulty low
pressure
protection control
Faulty indoor unit
electronic
expansion valve
Faulty
control
Faulty outdoor
unit electronic
expansion valve
Faulty
control
Low suction air
temperature of
indoor unit
Faulty suction air thermistor of indoor unit
Low suction air temperature of outdoor unit
Faulty outdoor air temperature thermistor of outdoor unit
High pipe
resistance
Inadequate refrigerant quantity
Moisture choke
Dirty evaporator
Decreased
fan airflow
rate
Decreased
fan output
High air
passage
resistance
Abnormal piping length
Bent or crashed pipe
Clogging of foreign particles
Stop valve closed
Faulty fan motor
Faulty control PCB
(Including capacity setting)
Dirty filter
Obstacle
Faulty low pressure sensor
Faulty control PCB
Faulty low pressure sensor
Faulty hot gas solenoid valve
Faulty control PCB
Faulty valve coil
Faulty valve body
Faulty gas pipe
thermistor of indoor unit
Faulty liquid pipe thermistor
of indoor unit
Faulty control PCB
Faulty valve coil
Faulty valve body
Faulty low pressure sensor
Faulty suction pipe thermistor
Faulty control PCB
Short circuit
Low outdoor air temperature
←
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
←
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
←
Are the electrical characteristics normal?
←
Are the coil resistance and insulation normal?
←
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
←
Are the coil resistance and insulation normal?
←
Check for the thermistor resistance and
connection.
←
Check for the thermistor resistance and
connection.
←
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
←
Are the coil resistance and insulation normal?
←
Are the electrical characteristics normal?
←
Check for the thermistor resistance and
connection.
←
Is the suction air temperature not less than 14°C
←
Is the indoor temperature not more than 14°C
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Is the outdoor temperature more than -20°C
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Does the piping length fall in the permissible range?
←
Conduct visual checks for pipe conditions.
←
Is there any temperature difference caused
before and after the filter or branch pipe?
←
Refer to P339.
←
Eliminate moisture by vacuum operation.
←
Is the heat exchanger clogged?
←
Can the fan motor be rotated with hands?
Are the motor coil resistance and insulation normal?
←
If a spare PCB is mounted, is the
capacity setting properly made?
←
Is the air filter clogged?
←
Is there any obstacle in the air passage?
*1: For details of the compressor capacity control while in cooling, refer to “Compressor PI Control”.
*2: The “low pressure protection control” includes low pressure protection control and hot gas bypass control.
*3: In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”.
*4: In heating, the outdoor unit electronic expansion valve (EVM) is used for “superheated degree control of
outdoor unit heat exchanger”.
SDK04009
←
Check to be sure the stop valve is open.
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...