Stopping Operation
3.7.1 When System is in Stop Mode (Normal operation stop)
This mode is used to define actuator operations when the system stops.
3.7.2 Stop due to Malfunction
In order to protect compressors, if any of the following items has an abnormal value, the system will make "stop with
thermostat OFF" and the malfunction will be determined according to the number of retry times.
Actuator
Symbol
Elect.
symbol
Operation
REYQ
REMQ
REYQ8~16P
REMQ8P
REMQ10•12P
REMQ14•16P
Compressor 1
—
M1C
M1C
OFF
OFF
OFF
OFF
Compressor 2
—
M2C
M2C
OFF
—
OFF
OFF
Compressor 3
—
M3C
M3C
—
—
—
OFF
Outdoor unit fan 1
—
M1F
M1F
OFF
OFF
OFF
OFF
Outdoor unit fan 2
—
M2F
M2F
OFF
—
—
OFF
Electronic expansion valve
(Main)
EVM
Y1E
Y3E
Y1E
0 pls
Electronic expansion valve
(Subcooling)
EVT
Y2E
Y5E
Y3E
0 pls
Electronic expansion valve
(Refrigerant charge)
EVJ
Y4E
Y2E
80 pls
Four way valve (Heat
exchanger switch)
20SA
Y2S
Y9S
Y3S
Holds
Four way valve (Dual
pressure gas pipe switch)
20SB
Y8S
Y2S
Holds
Solenoid valve (Main bypass)
SVE
Y5S
Y10S
Y6S
OFF
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
Solenoid valve (Refrigerant
regulator liquid pipe)
SVL
Y3S
Y4S
OFF
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG
Y1S
Y1S
OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVO
Y7S
Y7S
OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT
Y6S
Y8S
OFF
Ending conditions
—
Indoor unit thermostat is turned ON.
Item
Judgment Criteria
Malfunction Code
1. Abnormal low pressure level
0.07MPa
E4
2. Abnormal high pressure level
4.0MPa
E3
3. Abnormal discharge pipe temperature level
135
°
C
F3
4. Abnormal power supply voltage
Reverse-phase power supply
U1
5. Abnormal inverter current level
16.1A: 260 sec.
L8
6. Abnormal radiator fin temperature level
93
°
C
L4
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...