![Daikin REYQ8-48PY1B Service Manual Download Page 116](http://html.mh-extra.com/html/daikin/reyq8-48py1b/reyq8-48py1b_service-manual_502202116.webp)
Function General
SiBE37-701_B
105
Function
Symbol
Electric symbol
Description or function
REYQ8~16P REMQ8~16P
Ta
R1T (A1P)
R1T (A1P)
Outdoor air temperature
TsA
R8T (Suction
pipe1)
R8T
Suction pipe temperature
R10T
(Suction
pipe2)
Tb
R4T
(Deicer1)
R4T
Heat exchanger outlet temperature at cooling
R12T
(Deicer2)
Tg
R2T (Gas
pipe1)
R2T
Heat exchanger gas pipe temperature
R11T (Gas
pipe2)
Tf
R7T (Liquid
pipe1)
R7T
Temperature of liquid pipe between heat exchanger and main electronic expansion
valve
R15T (Liquid
pipe2)
Tsh
R5T (Gas
pipe1)
R5T
Temperature detected with the subcooling heat exchanger outlet thermistor
R13T (Gas
pipe2)
Tl
R6T (Liquid
pipe1)
R6T
Liquid pipe temperature detected with the liquid pipe thermistor
R14T (Liquid
pipe2)
Tsc
R9T
R9T
Temperature of liquid pipe between liquid stop valve and subcooled heat exchanger
Tc
–
–
High pressure equivalent saturation temperature
TcS
–
–
Target temperature of Tc
Te
–
–
Low pressure equivalent saturation temperature
TeS
–
–
Target temperature of Te
Tfin
R1T (A4P) (A5P)
R1T (A3P)
Radiation fin temperature
Tp
–
–
Calculated value of compressor port temperature
Tdi
R31T (R32T) R31T
Discharge pipe temperature of inverter compressor
Tds
R32T
R32T, R33T
Discharge pipe temperature of standard compressor
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...