SiBE37-701_B
Specifications
Specifications
34
Slim Concealed Ceiling Unit (with Drain Pump)
1-1 TECHNICAL SPECIFICATIONS
FXDQ20PBVE
FXDQ25PBVE
FXDQ32PBVE
Capacity
Cooling
kW
2.2
2.8
3.6
Heating
kW
2.5
3.2
4.0
Power Input
(50Hz)
Cooling
kW
0.086
0.086
0.089
Heating
kW
0.067
0.067
0.070
Power Input
(60Hz)
Cooling
kW
0.092
0.092
0.095
Heating
kW
0.073
0.073
0.076
Casing
Material
Galvanised steel plate
Dimensions
Unit
Height
mm
200
Width
mm
700
Depth
mm
620
Weight
Unit
kg
23
Heat
Exchanger
Dimensions Nr of Rows
2
2
3
Fin Pitch
mm
1.5
Face Area
m²
0.126
Nr of Stages
12
Fan
Type
Sirocco fan
Airflow Rate
Cooling
High high
m³/min
8.0
High
m³/min
7.2
Low
m³/min
6.4
Fan
External
static
pressure
High
Pa
30
Standard
Pa
10
Motor
Output
(high)
W
62
Drive
Direct drive
Cooling
Sound
Pressure
High high
dBA
33
High
dBA
31
Low
dBA
29
Piping
connections
Liquid
(OD)
Type
Flare connection
Diameter
mm
6.35
Gas
Type
Flare connection
Diameter
mm
12.7
Drain
Diameter
mm
VP20 (I.D. 20/O.D. 26)
Sound absorbing insulation
Foamed polyethylene
Air Filter
Removable/washable/Mildew proof
Refrigerant control
Electronic expansion valve
Temperature control
Microprocessor thermostat for cooling and heating
Safety devices
Fuse
Fan motor thermal protector
Standard
Accessories
Standard Accessories
Operation manual
Installation manual
Drain hose
Sealing pads
Clamps
Washer
Insulation for fitting
Clamp metal
Washer fixing plate
Screws for duct flanges
Air filter
Product Quality Certificate
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable to set by the remote control; this pressure means : high static pressure - standard
static pressure.
The operation sound levels are conversion values in anechoic chamber. In practice, sound levels tend to be higher than
the specified values due to ambient noise or reflection. When the suction place is changed to bottom suction, sound level
will increase
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...